port CN4 on the
KHA-12(14,16)RY3
outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4 in Part 4, 2. 3 "Main PCB for
Refrigerant System, Inverter Module").
2.
Final outlet water temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6 on the hydronic box
main
PCB (labeled 10 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
Domestic hot water tank temperature sensor connection is port
CN13 on
hydronic box main PCB (labeled 13 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
3.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s
resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 5-5.1 or 5-5.2 in Part 5, 5.1
“Temperature
Sensor Resistance Characteristics”.
4.
High pressure switch connection is port CN13 on the
KHA-06(08,10)RY1
outdoor unit refrigerant system main PCB (labeled 16 in Figure 4-2.2 in
Part4, 2.3 "Main PCB for Refrigerant System, Inverter Module"). port CN31 on the
KHA-12(14,16)RY3
outdoor unit refrigerant system main PCB
(labeled 20 in Figure 4-2.4 in Part 4, 2. 3 "Main PCB for Refrigerant System, Inverter Module").
5.
Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure
sensor
has failed.
6.
High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure
to
be lower than normal.
7.
Check air side heat exchanger, fan and air outlets for dirt/blockages.
8.
Check the water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages.
Midea CAC Confidential
M thermal Split
202004
81
4.19 P5 Troubleshooting
Digital display output
4.19.1
Description
4.19.2
High temperature difference between water side heat exchanger water inlet and water outlet
temperatures protection.
Split stops running.
Error code is displayed on hydronic box main PCB and user interface.
Possible causes
4.19.3
Temperature sensor not connected properly or has malfunctioned.
Water piping contains air.
Insufficient water flow.
Hydronic box main PCB damaged.
Midea CAC Confidential
Split
Содержание KMK-60RY1
Страница 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Страница 2: ...Split...
Страница 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Страница 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Страница 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 113: ...Split...
Страница 114: ...kaisai com...