For local insulation, be sure to insulate local piping
all the way into the pipe connections inside the unit.
Exposed piping may cause condensation or may
cause burns when touched.
Make sure that no oil remains on plastic parts of the
decoration panel (optional equipment).
Oil may cause degradation and damage to plastic
parts.
1 Piping insulation material(field supply)
2 Flare nut connection
3 Insulation for fitting (field supply)
4 Piping insulation material (main unit)
5 Indoor unit
6 Clamp (field supply)
A Turn seams up
B Attach to base
C Tighten the part other than the piping insulation material
Piping insulation procedure
Gas piping
Liquid piping
1
1
6
6
6
6
4
4
5
5
3
3
2
2
A
A
C
C
B
B
2) Be sure to insulate both the gas and liquid piping. Use
separate thermal insulation pipes for gas and liquid
refrigerant pipes. See the figure below.
Inter-unit wire
Liquid pipe
Liquid pipe
insulation
Drain hose
Finishing tape
Gas pipe
insulation
Gas pipe
- Keep piping as short as possible and slope it downwards at a
gradient of at least 1/100 so that air may not remain trapped
inside the pipe.
- Keep pipe size equal to or greater than that of the connecting
pipe (PVC pipe, nominal diameter 20mm in, outside diameter
25mm).
- Push the drain hose as far as possible over the drain socket,
and tighten the metal clamp securely.
4 CONNECT THE DRAIN PIPE
- Insulate the drain hose inside the building.
- If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).
1 Drain socket (attached to the unit)
2 metal clamp
3 Drain hose
4 Insulation (field supply)
- Make sure that heat insulation work is executed on the
following 2 spots to prevent any possible water leakage due
to dew condensation.
1 Indoor drain pipe.
2 Drain socket.
1
2
3
4
Install the drain pipes.
1.5m~2m
Insulating
material
Downward declivity
lower than 1/100
Bend
S shape
Put as deep as possible
(about 10cm)
Downward declivity
lower than 1/100
Vp30
Drainage test
- Check whether the drainpipe is unhindered.
- New built house should have this test done before paving the ceiling.
5 ELECTRIC WIRING WORK
General instructions
All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and national
regulations.
Use copper wire only.
A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.
- Gas pipes: might cause explosions or fire if gas leaks.
- Water pipes: no grounding effect if hard vinyl piping is used.
- Telephone ground wires or lightning rods: might cause
abnormally highelectric potential in the ground during
lightning storms .
Follow the 'Wiring diagram' attached to the unit body to wire the
outdoor unit, indoor units and the remote controller.
11
The specification of power
Minimum norminal cross-sectional
area of conductors:
Rated current
of appliance
(A)
Nominal cross-sectional
area
(mm2)
<6 0.75
>6 and <10 1.0
>10 and <16 1.5
>16 and <25 2.5
>25 and <32 4.0
>32 and <45 6.0
>45 and <60 10.0
NOTE:
The cable size and the current of the fuse or switch are determined by the
maximum current indicated on the nameplate which located on the side panel
of the unit. Please refer to the nameplate before selecting the cable, fuse and
switch.
MODEL(
)
Btu/h
55K
30K~36K 42K~55K
42K~48K
30K~36K
24K
18K
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
FREQUENCY AND VOLT
PHASE
CIRCUIT BREAKER/FUSE(A)
PHASE
15/10
15/10
15/10
15/10
15/10
15/10
15/10
208-240V 380-415V 380-415V
208-240V
208-240V
208-240V
208-240V
1Phase
1Phase
1Phase
1Phase
1Phase
1Phase
1Phase
1Phase
3Phase
3Phase
1Phase
1Phase
1Phase
1Phase
50/40
30/20
30/20
40/35
40/30
30/20
30/20
220-240V 220-240V 220-240V
220-240V
220-240V
220-240V
220-240V
POWER
(indoor)
POWER
(outdoor)
13
kaisai.com