background image

3    INSTALL THE REFRIGERANT PIPE

Execute heat insulation work completely on both sides of the 

gas piping and liquid piping. Otherwise, this can sometimes 

result in water leakage.

(When using a heat pump, the temperature of the gas piping can 

reach up to approximately 120 . Use insulation which is 

sufficiently resistant.)

Before rigging tubes, check which type of refrigerant is used.

All field piping must be provided by a licensed refrigeration

technician and must comply with the relevant local and 

national codes.

 

Use a pipe cutter and flare suitable for used refrigerant.

Do not mix anything other than the specified refrigerant, such 

as air, etc.., Inside the refrigerant circuit.

Coat the flare both inside and ouside with ether oil or ester oil .

If the refrigerant gas leaks during the work, ventilate the area. 

A toxic gas is emitted by the refrigerant gas being exposed to 

a fire.
Make sure there is no refrigerant gas leak. A toxic gas may be 

released by the refrigerant gas leaking indoor and being 

exposed to flames from an area heater, cooking stove, etc.

8

Also, in cases where the temperature and humidity of the

refrigerant piping sections might exceed 30  or Rh80%,

reinforce the refrigerant insulation(20mm or thicker).

Condensation may form on the surface of the insulating material.

Only use annealed material for flare conncetions.

Coat here with ether oil or ester oil

Precautions

3.1   Flaring the pipe end

1)  Cut the pipe end with a pipe cutter.
2)  Remove burrs with the cut surface facing downward so that the 

     chips do not enter the pipe.

5)  Check that the flaring is properly made.

Refer to the table below for the dimensions of flare nuts spaces 

and the appropriate tightening torque. (Overtightening may 

damage the flare and cause leaks.)

Pipe gauge

     (mm)

Outer diam.

     (mm)

Tightening torque

A(mm)

Max.

1.3
1.6
1.8
2.2

Min.

0.7
1.0
1.0
2.0

Flare dimension

         A (mm)

Flare shape

O6.35

O6.35

      15~16 N. m

(153~163 kgf.cm)

8.3~8.7

12.0~12.4

15.4~15.8

18.6~19.0

       25~26 N. m

(255~265 kgf.cm)
       35~36 N. m

(357~367 kgf.cm)
      45~47 N. m

(459~480 kgf.cm)

O9.52

O9.52

O12.7

O12.7

O15.9

O15.9

R0.4~0.8

45

2

90 4

A

o

o

1         Torque wrench

2         Flare nut

3         Piping union

4         Spanner     

1

2 3 4

Align the centres of both flares and tighten the flare nuts 3 or 4

turns by hand. Then tighten them fully with the torque wrenches.

3.2   Refrigerant piping

Check  whether  the  height  drop  between  the  indoor  unit  and 

outdoor unit, and the length of refrigerant pipe meet the following 

requirements:

Capacity

Btu/h

(

)

The type of models

Max.allowable 

piping length

25m

50m

<15000

R410A inverter

Split type air 

conditioner

Max.allowable 

piping height

10m

25m

30m

65m

>15000~<24000

>24000~<36000

>36000~<60000

20m

30m

Cut exactly at

right angles.

Remove burrs.

Flare

'

s inner surface

must be flaw-free

The pipe end must

be evenly flared in a 

perfect circle.

Make sure that the 

flare nut is fitted.

3)  Put the flare nut on the pipe.

4)  Flare the pipe.

Die

Copper pipe

A

Set exactly at the position shown below.

3.3   Purging air and checking gas leakage

    When piping work is completed, it is necessary to purge the

    air and check for gas leakage.

WARNING

   Do not mix any substance other than the specified refrigerant 

   into the refrigeration cycle. 

   When refrigerant gas leaks occur, ventilate the room as soon as 

   possible.

   The specified refrigerant should always be recovered and never 

   be released directly into the environment.

   Use a vacuum pump for the specified refrigerant. Using the 

   same vacuum pump for different refrigerants may damage the 

   vacuum pump or the unit.

   If using additional refrigerant, perform air purging from the

   refrigerant pipes and indoor unit using a vacuum pump, than 

   charge additional refrigerant.

   Use a hexagonal wrench(4mm) to operate the stop valve rod.

   All refrigerant pipe joints should be tightened with a torque 

   wrench at the specified tightening torque.

1)  Connect projection side of charging hose (which comes from 

     gauge manifold) to gas stop valve's service port. 

2)  Full open gauge manifold's low-pressure valve (Lo) and

     completely close its high-pressure valve (Hi)

     (High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound

     pressure gauge reads -0.1MPa (-76cmHg).*1 

4)  Close gauge manifold's low-pressure valve (Lo) and sop 

     vacuum pump.

     (Keep this state for a few minutes to make sure that the

      compound pressure gauge pointer does not swing back.)*2

5)  Remove caps from liquid stop valve and gas stop valve. 

6)  Turn the liquid stop valve's rod 90 degrees counterclockwise

     with a hexagonal wrench to open valve.

     Close it after 5 seconds, and check for gas leakage.

     Using soapy water, check for gas leakage from indoor unit's

     flare and outdoor unit's flare and valve rods.

     After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve's service port

    then fully open liquid and gas stop valves.

    (Do not attempt to turn valve rod byond its stop.)

8)  Tighten valve caps and service port caps for the liquid and

     gas stop valves with a torque wrench at the specified torques.

*1. Pipe length vs. Vacuum pump run time

9

3.5   Refrigerant pipig work

Pipe length and refrigerant amount:

Connective

pipe length

3.4   Additional refrigerant charge

CAUTION

Refrigerant may only be charged after performing the leak

test and the vacuum pumping.

Check the type of refrigerant to be used on the machine 

nameplate. Charging with an unsuitable refrigerant may

cause explosions and accidents, so always ensure that the

appropriate refrigerant is charged.

Refrigerant containers shall be opened slowly.

  

   The outdoor unit is factory charged with refrigerant. Calculate the 

   added refrigerant according to the diameter and the length of the 

   liquid pipe of the outdoor unit/indoor unit connection. 

1)  Caution on the pipe handling

     Protect the open end of the pipe against dust and moisture.

     All pipe bends should be as gentle as possible. Use a pipe

    bender for bending.

Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.

Pipe length

Up to 15m

More than 15m

Not less than 15min

Not less than 10 min

Run time

*2. If the compound pressure gauge pointer swings back,

      refrigerant may have water content or a loose pipe joint may 

      exists. Check all pipe joints and retighten nuts as needed, 

      then repeat steps 2) through 4).

Be sure to 

place a cap.

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Wall

Rain

Less 

than 5m

More 

than 5m

Air purging

method

Use vacuum

pump. 

Use vacuum

pump. 

Additional amount of refrigerant to be charged

                           

R410A: (L-5)x15g/m        

Liquid side:    6.35mm

R410A: (L-5)x30g/m        

Liquid side:    9.52mm

11

kaisai.com

Содержание 12K

Страница 1: ...PE INSTALLATION MANUAL Ceiling And Floor Type Thank you verymuch for purchasingour air conditioner Before using yourair conditioner please read thismanual carefully andkeep it forfuture reference INST...

Страница 2: ...If used as MULTI unit please refer to the Installation operation manuals packed with outdoor unit...

Страница 3: ...and firm location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance shall not be installed...

Страница 4: ...es a distance of 1 meter may not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditi...

Страница 5: ...some models 1 on some models 1 1 2 on some models 2 on some models 6 Remote controller 7 Frame 8 Mounting screw ST2 9 0 C H 9 Alkaline dry batteries Am4 10 Remote controllermanual 11 Wirecontroller 12...

Страница 6: ...eets the following requirements 1 INDOOR UNIT INSTALLATION All the pictures in this manual arefor explanation purpose only There may be slightly different fromthe air conditioner you purchased depend...

Страница 7: ...squaretimber traversely over the roof beam then install thehanging screw bolts Inlaying or embeddingthe screw bolts Use embedding screwbold crock andstick harness Timber over thebeam Roof beam Ceilin...

Страница 8: ...may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture Cannot be installed hanging from ceil...

Страница 9: ...atterns the wall height on the outlet side should be 1200mm or less 1 Installing outdoor unit 2 Drain work If drain work is necessary follow the procedures below Use drain plug for drainage If the dra...

Страница 10: ...il Precautions 3 1 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 5 Check that the flaring is pr...

Страница 11: ...the check is complete wipe all soapy water off 7 Disconnect charging hose from gas stop valve s service port then fully open liquid and gas stop valves Do not attempt to turn valve rod byond its stop...

Страница 12: ...tion Gas pipe Keep piping as short as possible and slope it downwards at a gradient of at least 1 100 so that air may not remain trapped inside the pipe Keep pipe size equal to or greater than that of...

Страница 13: ...it body to wire the outdoor unit indoor units and the remote controller 11 The specification of power Minimum norminal cross sectional area of conductors Rated current of appliance A Nominal cross sec...

Страница 14: ...m according to the figure 1 When attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insulati...

Страница 15: ...ndensed of by the air conditioner have influenced your neighborhood Whether any of the refrigerant is leaked A protection feature prevents the air conditioner from being activated for approximately 3...

Страница 16: ...for product improvement Consult with the sales agency or manufacturer for details QSDLI 016AEN CE 16122500000090 20150122 t to change without prior notice for product ncy or manufacturer for details 1...

Отзывы: