Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
cos-phi const.
0.3 - 1
F
Determine the prescribed shift factor.
.
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
4
1
2
3
4
Settling time
200 - 60000 [ms]
1000
Password protection
Status
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behavior corresponds to a first-order filter (PT-1) with settling time
= 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Q constant
NOTE: Define the Q constant.
4
1
2
3
4
Q constant
0 – 100%
F
Set the reactive power Q (in %) to a fixed value.
Under-excited |
over-excited
F
Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited relates to
capacitive load.
4
1
2
3
4
Increasing output gra-
dient & Decreasing
output gradient
1 - 65534 [% / min]
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
4
1
2
3
4
Settling time
200 - 60000 [ms]
1000
Password protection
Status
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behavior corresponds to a first-order filter (PT-1) with settling time
= 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Cos-phi
NOTE: More detailed information can be found in
F
Define the standard characteristic curve with 3 nodes.
4
1
2
3
4
Lock-In voltage
10 – 124.8 [%
Unom]
F
Set the voltage above which control is activated.
4
1
2
3
4
Lock-Out voltage
10 – 124.8 [% Unom]
F
Set the voltage below which control is deactivated.