No. Grid
LED
LED
Display on web interface
Status description
Action
Pers
.
181
Insulation error, centre
Insulation error close to the centre of the PV
string (area co-15% of the half of the
string)
As such, symmetri-
cal fault resistances
are also detected.
These must be recti-
fied in order to op-
erate the system
safely and reliably.
E
182
Insulation error, minus
See description in the event of a fault 181
See action in the
event of a fault 181
-
183
Insulation error, plus
See description in the event of a fault 181
See action in the
event of a fault 181
-
184
Protective shutdown over-
current L1 int.
See description in the event of a fault 181
See action in the
event of a fault 181
-
185
Protective shutdown over-
current L2 int.
See description in the event of a fault 181
See action in the
event of a fault 181
-
186
Protective shutdown over-
current L3 int.
See description in the event of a fault 181
See action in the
event of a fault 181
-
187
Fault in fan 4
Failure in the 3rd external fan or the corre-
sponding tacho signal. The power is not re-
duced. This occurs via the temperature dereg-
ulation. All 3 LEDs light up on the device.
Is the fan blocked?
For electrically
trained and quali-
fied personnel: Are
the plugs correctly
plugged in?
E
188
Semiconductor test not pos-
sible
Filter voltage measurement or actuation of the
semiconductors faulty.
Disconnect AC and
DC, wait 1 minute
and switch on again.
B
189
Semiconductor module 1 in
channel A defective
Semiconductor module x from channel A is de-
fective or the corresponding filter relay is not
closing correctly.
Disconnect AC and
DC, wait 1 minute
and switch on again.
B
190
Semiconductor module 2 in
channel A defective
See description in the event of a fault 189
See action in the
event of a fault 189
-
191
Semiconductor module 3 in
channel A defective
See description in the event of a fault 189
See action in the
event of a fault 189
-
192
Semiconductor module 1 in
channel B defective
See description in the event of a fault 189
See action in the
event of a fault 189
-
193
Semiconductor module 2 in
channel B defective
See description in the event of a fault 189
See action in the
event of a fault 189
-
194
Semiconductor module 3 in
channel B defective
See description in the event of a fault 189
See action in the
event of a fault 189
-
195
DESAT error
Saturation monitoring (DESAT) of the IGBTs
has tripped or the voltage supply (24 V) of the
gate drivers is too low.
-
-
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 101