Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
ROCOF threshold stage
1 value 0.1 – 6.0
[Hz / s]
ROCOF threshold stage
2 value 0.1 – 6.0
[Hz / s]
F
Define threshold for ROCOF
ROCOF threshold stage
1 time 0.10 – 5.00
[ s]
ROCOF threshold stage
2 time 0.10 – 5.00
[ s]
F
Define time value for ROCOF.
4
1
2
3
4
ROCOF proportionality
factor
-5000 – 5000 [
0
/
00
/
Hz]
Status
1 Define the proportionality factor.
2 Confirm the action field.
4
1
2
3
4
Ramp Rate Limitation
NOTE: Opportunity to limit power in the case of an increasing and de-
creasing grid frequency.
Operating mode
Status
F
Select operating mode.
Increasing gradient
1 – 65534 [%/min]
F
Set gradient.
Decreasing gradient
1 – 65534 [%/min]
Password protection
Status
F
Set gradient.
This percentage relates to the nominal frequency.
1 Activate optional password protection.
2 Confirm the action field.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Page 51