Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Minimum operating
voltage
45 – 125.0 [% Unom]
&
Maximum operating
voltage
45 – 125.0 [% Unom]
Password protection
Status
F
Set voltage range for the active control process.
4
1
2
3
4
Zero current threshold
undervoltage
0 – 80 [%Unom]
Zero current threshold
overvoltage
108 – 137 [%Unom]
F
Set voltage threshold for zero current mode.
If one or more phase/phase or phase/neutral conductor voltages move
below or above the configured threshold, the inverter changes to zero
current mode. The total current is regulated to virtually zero.
4
1
2
3
4
Reactive current limita-
tion
0 – 100 % [ % Imax]
F
Set the reactive power limitation.
4
1
2
3
4
Minimum support time
1000 – 15000 ms
F
Set the minimum support time.
4
1
2
3
4
Monitoring time PV
voltage
F
Set time for voltage monitoring.
Monitoring time grid
voltage
F
Set time for voltage monitoring.
4
1
2
3
4
Enhanced Island Detec-
tion
PLEASE NOTE: Grid operators require shutdown of the device with is-
landing detection
Advanced islanding detection [See section 10.5
4
1
2
3
4
ROCOF operation
mode passive Off |
On
F
Activate passive grid influence by application of a frequency.
ROCOF operation
mode active Off |
On
F
Activate active grid influence by application of a frequency.
4
1
2
3
4
Frequency shift
Off | On
F
Activate frequency shift.
4
1
2
3
4
Pulse period repetition
time
40 – 6000 [ms]
F
Define period for detection.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3