Country-
spec. Set-
tings
Level Display/
settings
Action in this menu/meaning
4
1
2
3
4
Frequency
NOTE: Opportunity to monitor frequency trip-off
Trip underfrequency
monitoring
Status
F
Activate, if necessary.
Number of underfre-
quency trip-off levels
1- 5
F
Specify the number of support levels.
Underfrequency trip-
off
42.5 – 65 [Hz] / &
underfrequency trip-off
time for levels 1 to 5
0 – 120000 [ms]
NOTE: If the grid frequency is within the deactivation range for the du-
ration of the deactivation time, then the function is deactivated.
F
Specify the range and trip-off time.
Trip overfrequency
monitoring
Status
F
Activate, if necessary.
Number of overfre-
quency trip-off levels
1- 5
F
Specify the number of support levels.
Overfrequency trip-off
45.0 – 67.5 [Hz] / &
overfrequency trip-off
time for levels 1 to 5
0 – 120000 [ms]
Password protection
Status
NOTE: If the grid frequency is within the deactivation range for the du-
ration of the deactivation time, then the function is deactivated.
1 Specify the range and trip-off time.
2 Activate optional password protection.
3 Confirm the action field.