Safety
Page 6
Installation Instructions KACO
blueplanet
32.0 TL3 / 40.0 TL3 / 50.0 TL3
2.1 Intended
use
The ISO-inverter converts clean renewable DC energy into AC energy for export into the utility. The inverter was designed
in accordance with UL 1741, CSA-C22.2 No. 107.1.01 and the NFPA 70. Authorized personnel who are qualifi ed for the VAC
and VDC voltage ratings are the only people who should install or maintain this equipment. Lethal hazards exist which
may result in serious injury.
Operate the inverter only with a permanent connection to the public power grid.
Any other or additional use of the device is deemed improper. This includes:
•
Mobile use,
•
Use in rooms where there is a risk of explosion,
•
Use in rooms where the humidity is higher than 95%,
•
Operation outside of the specifi cations intended by the manufacturer,
•
Standalone mode
2.2 Protection
features
For your safety, the following monitoring and protective functions are integrated into blueplanet inverters:
•
Overvoltage conductors/varistors to protect the power semiconductors from high-energy transients on the grid and
generator side,
•
Temperature monitoring of the heat sink,
•
EMC fi lters to protect the inverter from high-frequency grid interference,
•
Grid-side grounded varistors to protect the inverter against burst and surge pulses,
•
Islanding detection according to IEEE 1547
2.3
Standards and regulations
Electrical conformity according to U.S., Canadian and international safety operating standards and code
requirements:
•
UL 1741-2nd Ed 2010
•
NEC (2011)
•
CSA 22.2 No. 107-1:2001 Rev 2011
•
IEEE Std. 1547-2003
•
IEEE Std. 1547.1-2005
•
FCC Part 15 Class B
•
NFPA 70
•
Wiring method is accordance with the National Electrical Code ANSI/NFPA 70
•
Directive concerning Electromagnetic Compatibility with Class B (Council Directive 2004/108/EC)
•
Low Voltage Directive (Council Directive 2006/95/EC)
•
The Inverter has a on-board overcurrent protection for
DC
circuit.
•
The inverter has
no
internal overcurrent protection for
AC
circuit. The overcurrent protection for
AC
circuit must be
installed by authorized electricians.
•
The Inverter has a over-temperature and anti-islanding protection.