Maintenance/Troubleshooting
Page 44
Installation Instructions KACO
blueplanet
32.0 TL3 / 40.0 TL3 / 50.0 TL3
Status
Display
Explanation
Action
FS
34
Internal communica-
tion error
A communication error has occurred in
the internal data transmission.
Notify your author-
ised electrician.
E
Check the data
cable.
FS
35
Protection shutdown
SW
Protective shutdown of the
software (AC overvoltage, AC overcur-
rent, DC link overvoltage, DC overvolt-
age, DC overtemperature).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS
36
Protection shutdown
HW
Protective shutdown of the
hardware (AC overvoltage, AC overcur-
rent, DC link overvoltage).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS
38
Generator overvolt-
age error
The voltage of the DC generator is too
high. The PV generator is confi gured
incorrectly.
Notify your author-
ised electrician.
E
FS
41
42
43
44
45
46
Line failure:
undervoltage L1,
overvoltage L1,
undervoltage L2,
overvoltage L2,
undervoltage L3,
overvoltage L3
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your author-
ised electrician.
E
FS
47
Line failure: line-to-
line voltage
The measured line-to-line voltage is
outside of the tolerance limits. The
phase angle between the individual
phases of the three-phase supply net-
work is not correct, possibly no three
phase connection
Notify your author-
ised electrician.
E
FS
48
Line failure:
Under frequency
Grid frequency is too low.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
49
Line failure:
Over frequency
Grid frequency is too high.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
50
Line failure:
average voltage
The grid voltage measurement accord-
ing to EN 50160 has exceeded the
maximum permitted limit value.
This fault may be grid-related.
Notify your author-
ised electrician.
E
FS
57
Waiting for
reconnect
Waiting time of the inverter after a
fault.
Inverter does not switch on
again until the country-specifi c
time has elapsed.
FS
58
Overtemperature
Control card
The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.
Provide for suffi
cient
ventilation.
E
FS
59
Self test error
A fault occurred during a self-test.
Notify your author-
ised electrician.
E
OS
60
Generator
voltage too high
The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifi ed value.
-
-
Table 5:
Operating status and fault messages on the display