Installing the inverter
Installation Instructions KACO
blueplanet
32.0 TL3 / 40.0 TL3 / 50.0 TL3
Page 23
Connecting the fault signal relay
1. Route the connection cables into the connection area.
2. Connect the connection cables to the connection terminals.
7.4.3
Connecting the Ethernet interface
NOTICE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fi tting when it is installed.
For this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the
cable fi tting through the sealing insert.
NOTICE
Use a suitable category 5 network cable. The maximum length of a network segment is 100 m. Ensure that
the cable is correctly assigned. The Ethernet connection of the inverter supports auto-sensing. You can
use both crossed and 1:1 protectively-wired Ethernet connection cables.
Connecting an Ethernet cable to the inverter
1. Route the connection cables into the connection area.
2. Connect the connection cable to Ethernet interface.
3. Connect the provided ferrite clip above the cable fi tting to the Ethernet cable.
Connecting the inverter to the network
↻
Connect the Ethernet cable to the inverter.
↻
Confi gure the Ethernet interface in the confi guration menu.
Connect the Ethernet cable to the network or a computer.
Confi gure the Ethernet settings and the web server in the Settings menu.
7.4.4
Connecting the S0 output
An S0 pulse output is located on the communication board. Use this output to control accessories such as a large display,
for example. The pulse rate of the output is adjustable.
Connecting the S0 output
1. Route the connection cables into the connection area.
2. Connect the connection cables to the connection terminals.
NOTICE
Ensure that the wires are properly connected. Communication is not possible if the wires are reversed.
7.4.5
Connecting the RS485 bus (Modbus)
NOTE
Ensure that the DATA+ and DATA- wires are properly connected. Communication is not possible if the
wires are reversed.