11.6
Faults
11.6.1 Procedure
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device
has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
1. If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH
Service.
2. The operator can only carry out actions marked with a B.
NOTE
In case of power failure, wait for the system to automatically restart. Notify your electrician if there is an exten-
ded power failure.
11.6.2 Rectifying a fault
Fault
Possible cause
Explanation/remedy
By
The display is blank and
the LEDs do not light up
Grid voltage not avail-
able
› Check whether the DC and AC voltages are within the permit-
ted limits (see Technical Data)
E
› Notify KACO Service.
E
The device stops feeding
into the grid shortly
after being switched on,
even though there is
sunlight present.
Faulty grid separation
relay in the device.
If the grid separation relay is defective, the device will recog-
nise this error during the self-test.
K
› Ensure that there is sufficient PV generator power.
› If the grid separation relay is defective, have it replaced by
KACO Service.
› Notify KACO Service.
E
Device is active but is
not feeding into the grid.
The display indicates a
grid failure.
Grid-feed is interrupted
due to a grid fault.
Due to a grid fault (over/undervoltage, over/underfrequency),
the device stopped the feed-in process and disconnected from
the grid for safety reasons.
› Change the grid parameters within the permitted operating
limits (see the "Start-Up" section).
E
The grid fuse trips.
The grid fuse capacity is
too low.
In case of a high level of solar radiation, the inverter exceeds its
rated current for a short period, depending on the PV gener-
ator.
Select the capacity of the device’s backup fuse to be somewhat
higher than the maximum feed-in current (see the "Installa-
tion" section).
E
› Contact the grid operator if the grid failure continues to oc-
cur.
E
The grid fuse trips.
Hardware damage on
the device.
If the grid fuse trips immediately when the device goes into
feed-in mode (after the start-up period is complete), the
device’s hardware is probably damaged.
› Contact KACO Service to test the hardware.
E
The device is displaying
an impossible daily peak
value.
Faults in the grid.
The device continues to operate as normal without losses to
the yield, even when an erroneous daily peak value is dis-
played. The value is reset overnight.
To reset the value immediately, switch the device off by dis-
connecting it from the grid and switching off the DC, then
switch it back on.
E
Manual
Maintenance and troubleshooting | 11
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 77
EN