DC-side
Recommended cable type
AC-side
Max. conductor cross-section
10 mm²
Max. cable cross-section (without wire sleeves)
16 mm²
Length of insulation to be stripped off
18 mm
Connection type
Spring-type terminals
Fuse protection for installation provided by customer
at least 32A at 6.0mm²
Fitting for AC connection
M40
Cable diameter for cable fitting
16 - 28 mm
Torque for cable fitting
10 Nm
Interfaces
Interface screw connections
Ethernet: M25, default RS485: M16, max. 1.5 mm
Cable diameter for cable fitting
(2x) 8 - 17 mm
RS485 connection type
spring-type terminal
RS485 terminal cable cross-section
0.25 - 1.5 mm²
Ethernet connection type
RJ45
Torque for cable fitting
4 (M25) 1.5 (M16) Nm
Overvoltage protection
Type [KACO article no.]
Overvoltage protection for DC plug (integrated)
VAL-MS-T1/T2 1000DC-PV-ST - 2801162 [3010608] –
SPD I + II
VAL-MS 1000DC-PV-ST – 2800624 [23700379] – SPD II
Base integrated
VAL-MS/2+V-BE FM-PU40 – [2908425] – Phoenix Con-
tact
7.4
Connecting the device to the power grid
7.4.1
Make the grid connection
TN-S system, TN-C-S system, TT system
↻
Connection cable with 5 cores is available on the device.
↻
Rated mains voltage corresponds to nameplate specification VAC nom.
1. Loosen cable gland for AC connection. [ W_46]
2. Stripping AC cables.
3. Insert AC cables through the cable gland into the connection area.
4. Strip AC cables.[
sl 18 mm
]
5. Open the latch of the PCB terminal block.
6. Insert the cables below the terminal block according to the labeling.
7. Close the locking device of the PCB terminal block.
8. Check all connected cables for tight fit.
9. Tighten the cable gland. [ W_46 / 10 Nm]
ð
Make the mains connection.
PE
N
BU
L2
BK
L1
BN
GNYE
L3
GY
1
2
3
Fig. 17:
AC connection terminal, 5-pin
1 Connection terminal
2 Labelling
3 Colour code
7 | Installation
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 22
EN