Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Threshold activated
45 Hz – 70 Hz
F
Specify activation threshold (if mode 1 or mode 2 is active, this menu
option is displayed permanently for IT and IL!)
NOTE: The function is activated if the activation threshold is
exceeded. In mode 2 this value also serves as a deactivation
threshold.
4
1
2
3
4
Threshold deactivated
Min. 45 Hz – 61,5 Hz
Max. 45 Hz – 70 Hz
.
NOTE: If the grid frequency is within the deactivation
range for the duration of the deactivation time, then the
function is deactivated.
1. Specify deactivation threshold (if mode 1 or mode 2 is active, this
menu option is displayed permanently for IT and IL!).
Not for IL,
IT
4
1
2
3
4
Deactivation time
F
Specify time for power reduction (if mode 1 is active)
4
1
2
3
4
Gradient
F
Set gradient of power limitation function with increasing frequency
in % / Hz. The percentage value is based on the rated frequency (if
mode 1 or mode 2 is active, this menu option is displayed perman-
ently for IT and IL!)
4
1
2
3
4
Intentional delay
F
Set the power limitation delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Settling time
F
Set the power reduction delay in seconds (if mode 1 or mode 2 is act-
ive; this menu option is displayed permanently for IT and IL!).
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
F
Specify output gradient increase and decrease in
0
/
00
(per thousand).
4
1
2
3
4
Deact. grad.
F
Specify deactivation gradient in
0
/
00
(per thousand) /minute (if mode "1" or mode "2" is active. This
menu option is displayed permanently for IT and IL!).
4
1
2
3
Fault ride-through
NOTE: The device supports dynamic grid stabilization (Fault
Ride-Through).
F
Further parameterisation is possible via the web interface
4
1
2
3
Reactive power
1. Open the menu: Press the
Right arrow button
or
Enter
button
.
2. Activating reactive power process: Select process a press the
Enter button
. The active process is highlighted.
4
1
2
3
4
cos-phi const.
1- 0.3
More detailed information about the procedure can be found at:
2. Determine the specified displacement factor.
Over-excited | un-
der-excited
F
If a power factor not equal to 1 is selected: Select the type of phase
shift: under-excited (inductive load), over-excited (capacitive load).
4
1
2
3
4
Q constant
0 – 100%
More detailed information about the procedure can be found at: [See
section 10.1
F
Set the idle power Q (in %) to a fixed value.
Under-excited |
over-excited
F
Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited
relates to capacitive load.
9 | Configuration and operation
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 44
EN