Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
1 %-60000 %/min
F
Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
1 %-60000 %/min
F
Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
4
1
2
3
4
Min. cos-phi Q1 - Min.
cos-phi Q4
NOTE: In the event of a significant voltage deviation, the max-
imum reactive power adjustment range can be limited by a
minimum cos φ in order to prevent an excessive reactive
power supply and, as a result, a significant reduction in the
maximum active power that can be fed in.
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
4
1
2
3
4
Priority mode
Q priority | P priority
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cur-
rently available and fed in.
4
1
2
3
4
Active curve
1 - 4
F
Select active curve.
NOTE: Up to 4 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
4
1
2
3
4
Reset the curve
F
Reset active curve to the default setting.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends
on the selected grid type.
F
Specify the number of nodes for the Q(U) characteristic curve.
4
1
2
3
4
1st node … 10th node
Voltage | Reactive
power | Excitation
0 - max. voltage in
continuous operation
F
Enter the voltage of the node in volts.
0-100% [% S
max
]
F
Set the reactive power of the node as a percentage of the maximum
power.
Over-excited | un-
der-excited
F
If a reactive power not equal to 1 is selected: Select the type of
phase shift.
4
1
2
3
Exten. standalone grid
NOTE: Grid operators require shutdown of the device with
standalone grid detection.
F
Further parameterisation is possible via the web interface.
BE CH-NS
CY DE-NS
DK JP-50HZ
JP-60HZ
LU-NS TW
UD
4
1
2
3
Line error
NOTE: Display of grid faults.
F
To show the last 5 grid fault messages, press the
Show button.
4
1
2
3
Advanced features
F
Further parameterisation is possible via the web interface
4
1
2
3
4
Information
Open the menu: Press the right arrow button or the OK button.
9 | Configuration and operation
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 46
EN