4
1
2
3
4
Constant K positive se-
quence dip &
Constant K positive se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Constant K negative se-
quence dip
Constant K negative se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Dead band
0 - 100 [% Uref]
10.0
F
Set dead band in %.
4
1
2
3
4
Dynamic reactive cur-
rent only
Off | On
NOTE: With FRT mode activated, the pre-fault reactive current
can be added.
F
If necessary, activate pre-fault reactive current.
4
1
2
3
4
Dead band mode
Mode 1 | Mode 2
F
Select dead band mode for the active control process.
4
1
2
3
4
Reference voltage
U< - U>
F
Set reference voltage for the active control process.
4
1
2
3
4
Minimum operating
voltage
45 – 125.0 [% Unom]
&
Maximum operating
voltage
45 – xxx [% Unom]
Password protection
Status
F
Set voltage range for the active control process.
4
1
2
3
4
Zero current under-
voltage threshold
Zero current over-
voltage threshold
0 – 184 V / 253 – 340
V
F
Set the voltage threshold for zero current mode.
4
1
2
3
4
Reactive current limita-
tion
0 – 100 % [ % Imax]
F
Set the reactive power limitation.
4
1
2
3
4
Minimum support time
1000 – 15000 ms
F
Set the minimum support time.
4
1
2
3
Connection cond.
NOTE: The device checks the grid voltage and grid frequency.
The grid feed-in mode begins if the measurements are within
the set ranges.
F
Set minimum and maximum values for connection.
9 | Configuration and operation
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 48
EN