INSTRUCTION MANUAL

HYBRID SOLAR INVERTER

MODEL

SKU

SUN-6K-SG05LP1-EU

11537

IN CASE OF ANY QUERY/ISSUE WITH THE PRODUCT, PLEASE REACH OUT TO US AT: [email protected]

FOR MORE PRODUCTS RANGE, INQUIRY PLEASE CONTACT OUR DISTRIBUTOR OR NEAREST DEALERS. 

V-TAC EUROPE LTD. BULGARIA, PLOVDIV 4000, BUL.L.KARAVELOW 9B

MULTI-LANGUAGE MANUAL QR CODE

Please scan the QR code  to access the manual in 

multiple languages.

WEEE Number: 80133970

Summary of Contents for SUN-6K-SG05LP1-EU

Page 1: ...PRODUCT PLEASE REACH OUT TO US AT SUPPORT V TAC EU FOR MORE PRODUCTS RANGE INQUIRY PLEASE CONTACT OUR DISTRIBUTOR OR NEAREST DEALERS V TAC EUROPE LTD BULGARIA PLOVDIV 4000 BUL L KARAVELOW 9B MULTI LA...

Page 2: ...tructions 3 3 Battery connection 3 5 PV Connection 3 4 Grid connection and backup load connection 4 OPERATION 4 1 Power ON OFF 4 2 Operation and Display Panel 5 LCD Display Icons 5 1 Main Screen 5 2 S...

Page 3: ...01 d D d d Ws system h d D Z d d d Z for future reference d d K E W W E input short circuits W d...

Page 4: ...02 Z W D E W E W W ZD W d t Ws DWWd W K 1 2 5 8 10 11 12 9 6 3 4 7 13 16 17 15 14...

Page 5: ...03 2 2 Product Size D...

Page 6: ...WiFI GPRS phone Cloud services On Grid Home Load Generator ATS Grid connected Inverter Smart Load Battery Solar CT AC cable DC cable Grid connected Inverter Cloud services W W W K hW K t t DWW DWWd d...

Page 7: ...05 W W z t W D D h manual h t W...

Page 8: ...06 D W d W W W sK E E E Not in the cool air directly E E E W d...

Page 9: ...500mm 500mm 07 D Z W h...

Page 10: ...08 Z Model Wire Size t Cable mm 35 Torque value max 5 2Nm t 50 5 2Nm...

Page 11: ...09 W W h E D D connected d recommended cables W Z t t t t t D PP PP t t...

Page 12: ...KE W K B HM G V G S T Gen start up N O Relay Neutral Earth Bond 240V Coil ATS240V GV GS diesel generator startup signal relay coil open contact G V S RS 485 parallel_1 parallel_2 BMS 485 CAN DRMs Z Z...

Page 13: ...d 1 2 Temp sensor 11 ON 1 2 Inverter...

Page 14: ...12 d t t t t t t d E W input and output connectors d Z D W Z Model Wire Size Cable mm Torque value max t 4 1 2Nm t 6 6 1 2Nm t 6 1 2Nm t 6 1 2Nm t 1 2Nm...

Page 15: ...13 GRID LOAD GEN PORT L N PE L N PE L N PE GRID LOAD GEN PORT ON 1 2...

Page 16: ...14 Ws d E W D d K Ws Ws Ws d unit d Ws Ws t Ws Ws Ws Ws K Ws Model Wire Size t Cable mm 4...

Page 17: ...15 Ws D t Ws K s s Ws Ws K s s Ws d Ws Ws s Inverter Model 5KW SG05LP1 6KW SG05LP1 7 6KW SG05LP1 8KW SG05LP1 s s s s s Ws DWWd s Z E DWW d E DWW d 2 3 6KW SG05LP1...

Page 18: ...e CT Arrow pointing to inverter DDSU666 DIN RAIL METER 230V 5 60 A 800imp kWh 2 5 6 1 4 7 8 3 D L N N L N L N L Grid AC Breaker Ed 2 1 4 3 CHNT DDSU666 DDSU666 DIN RAIL METER 230V 5 60 A 800imp kWh 2...

Page 19: ...AC Breaker L N RS485 Output RS 485 GND Input W dZKE EASTRON SDM230 1 s d 2 3 B 4 GND KD 5 3 6 7 E A B N N 1 2 4 RS485B RS485A RS485 ON 1 2 L N Load L N PE L N PE L N PE Grid Gen Note Inverter RS 485...

Page 20: ...Loads Hybrid Inverter AC Breaker DC Breaker PV DC Breaker E BAR E BAR N BAR AC Breaker AC Breaker AC Breaker Load L L N PE or N PE Battery PV BMS Load L N PE Grid L L N PE N PE Grid CT CT Home Loads H...

Page 21: ...19 Inverter DC Breaker for battery SUN 3 6K SG 150A DC breaker SUN 5K SG 150A DC breaker SUN 6K SG 150A DC breaker SUN 7 6K SG 225A DC breaker SUN 8K SG 225A DC breaker AC Breaker for Gen port 2 SUN 3...

Page 22: ...d Gen Load L N PE L N PE L N PE Grid Gen Load L N PE L N PE L N PE Grid Gen The second side of the CT only needs to connect the master inverter CT CT Arrow pointing to inverter DC Breaker for battery...

Page 23: ...r inverter C Phase Master inverter A Phase Home load L3 L2 L1 N BAR E BAR AC Breaker AC Breaker AC Breaker DC Breaker DC Breaker DC Breaker CT1 CT2 CT3 CT Arrow pointing to inverter DC Breaker for bat...

Page 24: ...4 OPERATION W KE K K K K t Ws KE K K KE K EK K W d 22 LED Indicator DC Normal Z Ws D Messages h d d d d...

Page 25: ...23 D d d E yy yy W t D d t Ws 25 12 18 2020 09 21 00 Fri 1 85 KW 1 79 KW 0 04 KW 0 02 KW 0 7 0 5 0 5 0 5 ON...

Page 26: ...ar Page Solar Graph Grid Graph BMS Page Load Graph Battery Setting System Work Mode Grid Setting Gen Port Use Basic Setting Advanced Function Device info Grid Page Inverter Page Battery Page Load Page...

Page 27: ...L LD 0W Grid W Power 1560W Energy PV1 V 286V PV2 V 45V Today 8 0 KWH Total 12 00 KWH PV1 5 5A PV2 0 0A P1 1559W P2 1W Solar d W W W s W DWWd W d Power 0W Today 0 0 KWH Total 0 40 KWH L 0V Load Energy...

Page 28: ...0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0...

Page 29: ...c Setting System Setup Device Info Advanced Function Basic Set Time Syncs Beep Auto Dim 24 Hour Basic Setting Year Month Day Hour Minute Lock out all changes Factory Reset 2019 03 09 15 17 Z Z d out i...

Page 30: ...0A 40A 400Ah Batt Mode Use Batt No Batt h s h s s h h K D D t t t t D E to the system d Grid Charge Gen Charge Grid Signal Gen Signal Gen Force Battery Setting Start A 30 30 40A 40A Batt Set2 d W K E...

Page 31: ...TEMPCO mV C Cell Batt Resistance 30 days Equalization Hours 3 0 hours 25mOhms Battery Setting Set3 Batt Z d D W Float Stage Torque value Gel t D Lithium Mode Shutdown Low Batt Restart 40 20 10 00 Batt...

Page 32: ...First LoadFirst System Work Mode Solar Sell Solar Sell 5000 5000 Power 5000 Zero export Power 20 Selling First Work Mode1 Grid Peak Shaving t D d D d Ws W W 2 Grid d d d d d d Ws d d d d d d d load Gr...

Page 33: ...1 00 01 00 Power 5000 5000 5000 5000 5000 5000 49 0V 50 2V 50 9V 51 4V 47 1V 49 0V Work Mode2 K K K K K K K K K K Time Of Use Time System Work Mode Batt Grid Charge Gen 01 00 05 00 08 00 10 00 15 00 1...

Page 34: ...16S 0 16S 0 16S HF2 0 00HZ HF1 0 00HZ LF1 0 00HZ LF2 0 00HZ 0 16S 0 16S 0 16S 0 16S Grid Set4 For California only W D W d Grid Setting Grid Mode Grid Type General Standard UL1741 IEEE1547 CPUC RULE21...

Page 35: ...le Phase CEI 0 21 Grid Set1 Grid Warning Grid Mode CEI 0 21 Grid Type 50Hz 220V Single Phase CANCEL OK d K PassWord DEL X X X X 1 2 3 4 5 6 7 8 9 CANCEL 0 OK Solar Arc Fault ON Clear Arc_Fault System...

Page 36: ...elfcheck BMS_Err_Stop 0S 2000 1 Backup Delay Advanced Function Func Set1 DRM Gen peak shaving CEI 0 21 Report CT Ratio Signal ISLAND MODE Inverter ID 2012041234 Self Test Report 59 S1 threshold253V 90...

Page 37: ...t SmartLoad Output Micro Inv Input On Grid always on GEN PORT USE 52 00Hz 100 95 Power Rated Power AC Couple Fre High 500W 8000W PORT Set1 GEN connect to Grid input AC couple on grid side AC couple on...

Page 38: ...unction Paral Set3 A Phase 0 4 B Phase B Phase A Phase C Phase CHNT 1P Eastron 3P Eastron 1P coil external relay open contact L N ATS load port Inverter shell Ground cable 230V Solar Arc Fault ON Clea...

Page 39: ...0 0 0 50 30V 16 90A 30 2C 12 0 6 0Ah 53 2V 25 0A 0 0 0 4 5 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A...

Page 40: ...AC cable DC cable Smart Load D t D s On Gen AC couple AC cable DC cable CT Battery Solar Grid Backup Load On Grid Home Load On Grid Inverter On Load AC couple AC cable DC cable CT Battery Solar Grid B...

Page 41: ...39 d can operate reliably K d is as detailed as possible z d Ws d d z On Grid AC couple AC cable DC cable CT Battery Solar Grid Backup Load On Grid Home Load On Grid Inverter Smart Load...

Page 42: ...mal state DC side over current fault 1 Check PV module connect and battery connect 2 When in the off grid mode the inverter startup with big power load it may report F20 Please reduce the load power c...

Page 43: ...y is in the range of specification or not 2 Check whether AC cables are firmly and correctly connected 3 Seek help from us if can not go back to normal state F56 DC busbar voltage is too low Battery v...

Page 44: ...42 d h product...

Page 45: ...D s s s s s s s 2 D K W t W W D D W W K Z E W DWWd d AC Output Data Z K hW W t E W s W K s Grid Type d d D DWWd W W Ws W Ws Z W W Z d d W K W Z D h K K W t 3600 3960 SUN 3 6K SG05LP1 EU t 5000 5500 SU...

Page 46: ...44 Z D Z General Data W K d Z E D t t Z E 24 t W 5 years t E E E E E E s s E hE E Z E Z...

Page 47: ...45 Z W W D 1 No RS485B RS485 Pin CAN Pin 2 RS485A GND 3 GND 4 CANH 5 CANL 6 GND 7 RS485A 8 RS485B 1 2 3 4 5 6 7 8 D W E W 8 7 6 5 4 3 2 1...

Page 48: ...46 Z W W Z d 4 No RS485B RS485 Pin 5 RS485A 1 2 3 4 5 6 7 8 Z W...

Page 49: ...47 Z WIFI RS232 1 No D GND WIFI RS232 2 3 4 5 6 TX 7 12Vdc 8 1 2 3 4 5 6 7 8 9 RX 9 d Z...

Page 50: ...48 d d K Ver 2 2 2022 10 10...

Page 51: ...e If you have any another query please contact our dealer or local vendor from whom you have purchased the product They are trained and ready to serve you at the best INTRODUCTION IN CASE OF ANY QUERY...

Page 52: ...test manual from www vtacexports com or sales Unless otherwise agreed herein this manual will only be used as guidance Any statement information or suggestion in this manual will not take any form of...

Page 53: ...ove the Module 1 WIFI MODULE INSTALLATION Implication Lights Status Description All lights are single green lights Communication with router Communication with inverter WIFI Module running status 1 Li...

Page 54: ...cess to the network 2 Check the router s setting if the connection is limited 3 Contact our customer service 1 Check the connection between WIFI Module and inverter Remove the WIFI Module and install...

Page 55: ...methods and key press descriptions for Reset button NOTICES FOR RESET BUTTON USER MANUAL FOR SOLARMAN SMART APP Notice Do not remove waterproof plug Key press Status Descrip on Light Status Short pre...

Page 56: ...packaging or on the logger body 4 Network Configuration After the logger is added please configure the network to ensure normal operation Go to Plant Details Device List find the target SN and click...

Page 57: ...heck plant data Usually the data will be updated in 10 mins If configuration failure occurs please check the following reason and try it again 1 Make sure WLAN is ON 2 Make sure WiFi is normal 3 Make...