Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Parameters
F
Press the
Right arrow button
or
Enter button
.
NOTE: The device does not display the "Parameters" menu in
the standard configuration. To display the Parameters menu:
1. Open the menu.
2. Simultaneously hold down the
Up
and
Down buttons
for sev-
eral seconds.
4
1
2
3
4
Password protection
Status
On/Off
NOTE: Opportunity to set password protection.
F
Selecting "yes" initiates a password request for the entire menu
item:
Parameters
.
4
1
2
3
Country
NOTE: This option influences the country-specific operating
settings of the device. Please consult KACO service for further
information.
1. Enter the four-digit password using the 4-way button. The password
is device-specific.
2. Confirm the entry with the
Enter
button.
3. Set the desired country setting.
CH, DE, ES,
FR, GB, GR,
IT, JO, JP,
LU, TH, ZA
4
1
2
3
Grid type/guideline
F
Select the grid type for the device’s installation location.
UD
4
1
2
3
Nominal grid voltage
F
Set the specified grid voltage for the site where the device is used
(please contact KACO Service)
4
1
2
3
Grid parameter
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
AT, BG, CZ,
FR-OLD,
FR-VFR13,
FR-VFR14,
IE, JP, NL,
PL, PT, TR,
TW, UD
4
1
2
3
Overvoltage shutd. 10
min. mean value
1. Specify the shutdown threshold for overvoltage trip-off.
ð
The 10-minute average for the measured voltage as per
EN50160 is used.
2. Set period from occurrence of the fault to shutdown of the device.
BE CH-NS
CY DE-NS
DK LU-NS
4
1
2
3
Overvoltage shutd. 10
min. mean value Pass-
word protection
1. Activate or disable password protection.
2. Specify the shutdown threshold for overvoltage trip-off.
ð
The 10-minute average for the measured voltage as per
EN50160 is used.
3. Set period from occurrence of the fault to shutdown of the device.
AT FR-OLD
FR-VFR13
FR-VFR14
JP-50HZ
JP-60HZ
UD
4
1
2
3
Voltage drop
NOTE: The voltage drop between the device and the feed-in
meter is added to the limit value that was set for grid shut-
down according to EN 50160. The limit value can be set to
0-11 Volt increments.
F
Specify the shutdown value for the voltage drop (0-11 Volt).
9 | Configuration and operation