NOTE:
Only one of the labels, INTAKE or EXHAUST, is visible through the vents of the installed
fan tray.
The color of the label visible through the vents of the installed fan tray must match the color of the ejector
lever on the installed power supply. The color match indicates that the power supply has the correct airflow
for this model. See
“AC Power Supply in EX4500 Switches” on page 58
CAUTION:
To prevent overheating of the chassis, verify that the color of the label
visible through the vents of the installed fan tray matches the color of the ejector lever
of the installed power supply. A color match indicates that the direction of airflow
through the fan tray matches the direction of airflow of the power supply.
Temperature sensors in the chassis monitor the temperature within the chassis. The fan tray used in the
switch comes with load-sharing redundancy that can tolerate a single fan failure at room temperature
(below 113° F/45° C) to still provide sufficient cooling.
Under normal operating conditions, the fans in the fan tray run at less than full speed. If a fan fails or the
ambient temperature rises above the threshold 113° F (45° C), the speed of the remaining fans is
automatically adjusted to keep the temperature within the acceptable range, 32° F (0° C) through 113° F
(45° C).
The system raises an alarm if the fan fails or if the ambient temperature inside the chassis rises above the
acceptable range. If the temperature inside the chassis rises above the threshold temperature, the system
shuts down automatically.
You can check the status of fans and the chassis temperature from the Environment Status option in the
Status menu on the LCD panel. See
“LCD Panel in EX4500 Switches” on page 38
.
You cannot replace a single fan. If one or more fans fail, you must replace the entire fan tray.
RELATED DOCUMENTATION
Clearance Requirements for Airflow and Hardware Maintenance for EX4500 Switches | 81
57
Содержание EX4500 Series
Страница 1: ...EX4500 Switch Hardware Guide Published 2020 12 15...
Страница 19: ...1 CHAPTER Overview EX4500 System Overview 20 EX4500 Chassis 35 EX4500 Cooling System 54 EX4500 Power System 58...
Страница 42: ...Table 6 LCD Panel Menu Options in EX4500 Switches continued Description Menu MAINT Maintenance Menu 42...
Страница 164: ...Table 47 System Information continued Description Field Inventory details 164...
Страница 240: ...5 CHAPTER Troubleshooting Hardware Troubleshooting EX4500 Components 241...
Страница 273: ...273...
Страница 280: ...Restricted Access Warning 280...
Страница 284: ...284...
Страница 297: ...Jewelry Removal Warning 297...
Страница 300: ...Operating Temperature Warning 300...
Страница 310: ...DC Power Disconnection Warning 310...
Страница 314: ...DC Power Wiring Sequence Warning 314...
Страница 317: ...DC Power Wiring Terminations Warning 317...