Figure 39: Remove Plastic Cover from Terminal Block
g020862
DC terminal block
DC terminal
block cover
3. Remove the locking screws from each DC power input terminal, using the screwdriver.
4. Ensure that the power source circuit breaker is open so that the voltage across the DC power source
cable leads is 0 V and that the cable leads do not become active while you are connecting DC power.
5. Verify that the DC power cables are correctly labeled before making connections to the power supply.
In a typical power distribution scheme where the return is connected to chassis ground at the battery
plant, you can use a multimeter to verify the resistance of the –48V and RTN DC cables to chassis
ground:
•
The cable with very high resistance (indicating an open circuit) to chassis ground is negative (–) and
will be installed on the –48V (input) DC power input terminal.
•
The cable with very low resistance (indicating a closed circuit) to chassis ground is positive (+) and
will be installed on the RTN (return) DC power input terminal.
CAUTION:
You must ensure that power connections maintain the proper polarity.
The power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the
external DC power source at your site determines the color coding for the leads
on the power cables that attach to the DC power input terminals on each power
supply.
WARNING:
Ensure that the power cables do not block access to switch components
or drape where people can trip on them.
NOTE:
To supply sufficient power, terminate the DC input wiring on a facility DC source
that is capable of supplying a minimum of 20 A at –48 VDC.
133
Содержание EX4500 Series
Страница 1: ...EX4500 Switch Hardware Guide Published 2020 12 15...
Страница 19: ...1 CHAPTER Overview EX4500 System Overview 20 EX4500 Chassis 35 EX4500 Cooling System 54 EX4500 Power System 58...
Страница 42: ...Table 6 LCD Panel Menu Options in EX4500 Switches continued Description Menu MAINT Maintenance Menu 42...
Страница 164: ...Table 47 System Information continued Description Field Inventory details 164...
Страница 240: ...5 CHAPTER Troubleshooting Hardware Troubleshooting EX4500 Components 241...
Страница 273: ...273...
Страница 280: ...Restricted Access Warning 280...
Страница 284: ...284...
Страница 297: ...Jewelry Removal Warning 297...
Страница 300: ...Operating Temperature Warning 300...
Страница 310: ...DC Power Disconnection Warning 310...
Страница 314: ...DC Power Wiring Sequence Warning 314...
Страница 317: ...DC Power Wiring Terminations Warning 317...