Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
60% to 40%
70% to 30%
80% to 20%
90% to 10%
room temperature.
Internal sensor
calibration
(-128...127) * 0.1 K
-128...
13
...127
Determines the value by which the
internal sensor’s room temperature
value is calibrated.
This parameter is only visible when the
temperature detection system requires
an internal sensor.
External sensor
calibration
(-128...127) * 0.1 K
-128...
0
...127
Determines the value by which the
external sensor’s room temperature
value is calibrated.
This parameter is only visible when the
temperature detection system requires
an external sensor.
Scanning time for
external sensor
(0...255) * 1 min;
0 = inactive
0
... 255
The polling time for the external sensor’s
temperature value is specified here. In
the "0" setting, the external sensor is not
automatically polled by the controller. In
this case, the sensor must transmit its
temperature value itself.
Transmission when
room temperature
change by
(0..255) * 0.1 K; 0 = No
automatic transmission
0 ... 255,
3
Determines the size of the value change
of the room temperature after which the
current values are automatically
transmitted on the bus via the "Actual
temperature" object.
Cyclical transmission of
room temperature
(0...255) * 1 min; 0 =
inactive
0 ... 255,
15
This parameter specifies whether and
when the determined room temperature
is to be periodically output via the
"Actual temperature" object.
Page 288 of 309
Software "Room controller display compact module 146x11"
Parameters