Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
For heating and cooling functions, you can select continuous or switching PI or switching 2-point
feedback control algorithms.
The controller distinguishes between different operating modes (comfort, standby, night,
frost/heat protection) each with their own temperature setpoints for heating or cooling.
Room temperature measurement:
The product database of the device contains three independent blocks for room temperature
measurement. Up to three temperatures can be determined in parallel, when the device is
installed combined with a TSEM and/or with a connected remote sensor. With a device
installation without TSEM and a remote sensor, a room temperature can be determined on the
device. Each room temperature measurement can be performed by the internal sensor or,
optionally, by a received temperature value. Combined temperature recording (internal
received temperature value) can also be configured.
Push-button sensor functionality:
When a rocker or button is pressed, the device transmits telegrams to the KNX, depending on
the ETS parameter settings. The following functions can be set: Switching, dimming, Venetian
blind, 1-byte value transmitter and 2-byte value transmitter. Using the value transmitter
functions, values between 0 and 255, 0 and 100%, 0 and 65535, temperature values (0...40°C)
or brightness values can be transmitted to the KNX according to the parameters.
In addition, when a rocker or a button is actuated, the device can execute the Scene extension
function, 2-channel operation or a change of the display.
A configured button can also operate one of the internal controllers or affect one of the two
controller extensions.
The operation concept of two operating elements can be configured in the ETS either as a
rocker function or alternatively as a button function. With the rocker function, two control
elements work together and execute a basic function. In the button function, each operating
element is evaluated separately.
With the rocker function, similar buttons are arranged "horizontally" (left-right operation). Thanks
to full-area operation, additional special functions can be triggered if a rocker function is
designed.
The compact 2-gang room controller possesses two status LEDs for each control surface.
The compact 4-gang room controller possesses one status LED for each control surface.
The status LEDs can be internally connected to the operating function, according to the function
of the rocker or button. Each status LED can then also signal completely independent display
information, operating states of room temperature controllers or indicate the results of logic
value comparisons, flash or be permanently switched on or off.
LED functions:
The compact room controller module possesses eight status LEDs. The status LEDs are
executed in three colours and can – according to choice, in either red, green or blue – be
switched on or off permanently or can function as an operation display or as a status display.
Furthermore, different statuses of the internal controller can be displayed. As an alternative, with
the aid of separate communication objects, they can signal widely varying display information
completely independently of the pushbutton function, e.g. operation states of fault messages or
also room temperature controllers, the results of logic value comparisons, flash or be
permanently switched on or off. Each colour of a status LED can be controlled either by three
separate objects or alternatively by a mutual object (superimposed function), so that traffic light
functions can also be implemented, - for example, depending on a limiting value - by means of
an LED. When switched-off, the status LEDs can shine in a designed colour, creating an
orientation light. The brightness of the status LED can be set to five levels. Through night
reduction, the brightness of the status LED can be reduced at night using a communication
object.
The active programming mode on the TSM is indicated by changing the colour of status LED 1
and status LED 2 between red and blue. The active programming mode continues to be
displayed by the "Prog" message in the display of the TSM. When a TSEM is connected, the
backlighting and the operation LED flash when the TSM is in programming mode.
Page 6 of 309
Product definition