Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Top hysteresis of the
2-point controller
cooling
(5 ... 127) * 0.1 K
5
...127
Definition of top hysteresis (switch-on
temperatures) of the cooling.
This parameter is only visible if "Type of
cooling control = Switching 2-point
feedback control (ON/OFF)".
Additional stage inhibit
object
Yes
No
The additional stages can be separately
disabled via the bus. The parameter
enables the disable object as necessary.
This parameter is only visible in two-
level heating and cooling operation.
Operating mode switch-
over
via value (1 byte)
via switching (4 x 1 bit)
In the setting "Via value (1-byte) the
change-over of the operating modes via
the bus takes place according to the
KNX specification via a 1-byte value
object. In addition, a higher-ranking
forced object is available for this setting.
In the setting "Via switching (4 x 1 bit)"
the ‘classic’ change-over of the
operating modes via the bus is via four
separate 1-bit objects.
Operation mode after
reset
Comfort mode
Standby mode
Night operation
Frost/heat protection mode
This parameter specifies which
operating mode is set immediately after
a device reset.
Frost/heat protection
Automatic frost protection
via window status
In addition to the operating mode
switchover by the corresponding
operating mode switchover object or by
room temperature regulator operation on
the TSM (button function), the frost/heat
protection mode can by activated by a
window contact or, alternatively, frost
protection can be activated by an
automatic temperature control option.
This parameter defines the manner in
which the higher-priority switchover
takes place, compared to the operating
mode switchover by an object or button
function.
Window status delay
(minutes, 0 = inactive)
0
... 255
You can optionally parameterise a
window status delay. This delay can
make sense if short ventilation of the
room by opening the window is not
supposed to cause an operating mode
switchover. You can use the "window
status delay" parameter to set this delay
time between 1 and 255 minutes. The
window status will only be changed and
thus the frost/heat protection mode
activated after this parameterized time
Page 263 of 309
Software "Room controller display compact module 146x11"
Parameters