Art. No. ..5192KRMTSD
Art. No. ..5194KRMTSD
Ľ
"Frost/heat protection" operating mode active. Flashes on frost alarm.
Frost alarm is dependent on an active "Controller status":
- For "KNX-conformant" ("Frost protection setpoint (°C) fallen below),
- For "General controller" (T
Room
<= +5 °C / +41 °F),
- For "Transmit individual state" (T
Room
<= +5 °C / +41 °F).
ļĺ
A "Night comfort extension" is active.
ļĽ
A "Frost/heat protection comfort extension" is active.
----
·
----
Indication of the basic setpoint in the positive "
·
- - - -
" or negative "
- - - -
·
" direction. A bar corresponds to shifting by one level value. The value of a level can be
parameterised in the ETS. If no shift is active, only "
·
" is displayed.
ş
Display of a fan controller configured in the ETS (impeller) with display
of the active fan level
Ŝ
,
ŝ
,
Ş
, ...,
ş
.
If no icon is displayed, either the fan control is completely deactivated in the ETS or the
fan function is activated in the ETS but is switched off.
Ť
The controller uses this icon to signal that heating energy is being fed to the room. In
continuous feedback control, the command value is indicated by the number of streaks
that are visible (0 %) , (1...20 %), (21...40 %), (41...60 %), (61...80 %), (81...100 %) .
In 2-point feedback control,
Ť
indicates a command value that is switched on and
Ţ
one
that is switched off.
This icon
Ť
is also visible in the menu level for setpoint temperature settings for heating
mode.
ŵ
The controller uses this icon to signal that cooling energy is being fed to the room. In
continuous feedback control, the command value is indicated by the number of streaks
that are visible (0 %) , (1...20 %), (21...40 %), (41...60 %), (61...80 %), (81...100 %) .
In 2-point feedback control,
ŵ
indicates a command value that is switched on and
ť
one
that is switched off.
This icon
ŵ
is also visible in the menu level for setpoint temperature settings for cooling
mode.
Table: Meaning of the display icons
Display information
In addition to the icons, it is possible to use the numeric display to show up to 17 display
functions in the display. Thus, up to 17 pieces of display information (actual temperature,
setpoint temperature, outdoor temperature, any temperature) can be optionally displayed with
the room temperature controller icons.
In the ETS, it is possible to configure which of this information is actually shown in the display.
In the "No display" setting, no information is shown in the display on recalling the appropriate
display.
The information is shown separately on the display. It is possible to change over between the
information automatically after set times or in a controlled manner by pressing a button on the
device. The display information are switched in the sequence Display 1, Display 2, Display 3, ...,
Display 17.
The following four figures show the possible display information in a sample sequence. Various
temperatures, received by input objects of the controller or the display, are shown. In this
application, Controller 1 works as the main controller and Controller 2 works as a controller
extension.
Page 89 of 309
Software "Room controller display compact module 146x11"
Functional description