Frost/heat protection
Table 7: Status of the communication objects and the resulting operating mode
X: Status irrelevant
-: Not possible
i
When changing over an operating mode, for example through local control, the KONNEX
switching object is updated by the controller and can be read out when the "Read" flag is
set. If the "Transmit" flag has been set for this object the current value will, in addition, be
automatically transmitted to the bus when it is changed.
After bus voltage recovery or after initialisation of the controller, the value corresponding to
the set operating mode will be actively transmitted to the bus if the "Transmit" flag has been
set. The "Transmit" flag must always be set when using controller extensions.
i
Change-over by the KONNEX object "Operating mode change-over" has the same priority
as a local change-over on the push-button sensor. An operating mode set by the object
(e.g. by a controller extension) can therefore be shifted by an operating mode change-over
on the device, if no higher-priority mode (e.g. window contact / presence detector) or the
KONNEX forced object is activated.
The KONNEX override object will always have the highest priority.
i
In parameterisation of a presence button: the presence object will be active ("1") for the
period of an active comfort extension. The presence object will be automatically deleted
("0") if the comfort extension is stopped after the extension time has elapsed, or if the
operating mode has been changed by a higher-priority operation through the change-over
objects or by local control or a forced operating mode is deactivated by the KONNEX
forced object (forced object -> "00"). The controller therefore automatically resets the status
of the presence button when an object value is received via the operating mode objects or
the forced object is reset.