18
7.5.2 HOW
7.5.2.1
Press the CAL/MODE button twice.
7.5.3 PROCESS
7.5.4.1
While in any stage of the calibration mode, pressing any
key other than enter or not pressing any key within 30
minutes will revert the system back to normal operation.
7.5.4.2
After pressing the CAL/MODE button TWICE the
following message will be displayed:
LAST CALIBRATION: XX/XX/XX PRESS ENTER TO
START, ANY OTHER KEY TO EXIT
7.5.4.3
After pressing ENTER the following message will be
displayed:
1.FILL TANK TO LEVEL ONE MARK (LOWER)
THEN PRESS ENTER TO RECORD LEVEL ONE
7.5.4.4
Prior to putting any water into the tank, ensure that the
tank is level and free of any grease or solids. After filling
the tank with water to level one of the calibration mark,
allow the water to settle and press ENTER the following
message will be displayed:
7.5.4.5
Reading level of one will take a few seconds. After the
system reads the calibration level the following message
will be displayed:
LEVEL 1 CALIBRATION
SUCCESSFUL
7.5.4.6
After a few seconds the following message will be
displayed:
2.FILL TANK TO LEVEL TWO MARK (UPPER)
THEN PRESS “ENTER” TO RECORD LEVEL TWO
7.5.4.7
After filling the tank to level two of the calibration mark,
allow the water to settle, and press ENTER the following
message will be displayed:
READING LEVEL TWO CALIBRATION
WAIT
READING LEVEL ONE CALIBRATION
WAIT