 16

WARNING, DO NOT RUN PUMP DRY!  

The system has been pre-

calibrated at the factory, prior to shipping, to ensure a suitable 
pump time and water sense level. However, if adjustments have 
been made it is important to ensure that pump does not run dry!  

 

6.3.5 

After the pump cycle is complete, the controller will beep again and 
the following message will be displayed: 

 

    AUTOMATIC CLEAN CYCLE COMPLETE  
   

 

6.3.6 

After the indication of the cycle being complete the horn will sound 
and the unit will wait for the water level in the tank to rise above the 
pump inlet. The following message will be displayed: 

 

 

 

6.3.7 

Once the level rises, the unit display will cycle to the main 
automatic mode.  

 

7. CALIBRATION 

MODE 

 

7.1 WHEN 

7.1.1 

The calibration mode is intended to enter the date, pump run time 
and calibrate the probe for measuring grease. It is important to note 
that the probe calibration senses the water level in the tank. 
Therefore, the tank should not have any grease introduced into the 
system. 

The time/date, pump run time and the probe calibration 

should typically be checked at a minimum of once a year. 

 

 

7.2 HOW 

7.2.1 

Open the controller enclosure and push the CAL/MODE button. 
The following message will be displayed: 

 

PRESS UP/DWN KEYS FOR DESIRED CAL 
 PRESS ENTER TO CHANGE TIME AND DATE 

 

7.3 

CANCELLING THE CALIBRATION MODE 
7.3.1 

Pressing the CANCEL button TWICE at any point during the 
calibration mode will exit the calibration mode and revert to the 
previous calibration values. Pressing the CANCEL button ONCE 
will display the following message: 

 

 

PRESS CANCEL KEY AGAIN TO EXIT CAL MODE 

 THIS LINE WILL DISPLAY AS PREVIOUS

 

 
 
 

       AUTOMATIC CYCLE COMPLETE 
        WAITING FOR LEVEL TO RISE   

Содержание 60305A

Страница 1: ...ON AND MAINTENANCE MANUAL PLEASE READ CAREFULLY Grease Recovery Device will operate efficiently only when properly installed Do not discard this manual Manual to be distributed to installer operator a...

Страница 2: ...E 10 11 CONTROLLER OPERATING PROCEDURES 13 21 CONTROLLER WARNINGS 12 UNIT INITIALIZATION 12 EXTERNAL CONTROLS 12 ENCLOSURE CONTROLS 13 MANUAL CYCLE 13 14 AUTOMATIC CLEAN CYCLE 15 16 CALIBRATION MODE 1...

Страница 3: ...ent Any damage should be reported to Josam Company immediately The following items should be included with the shipment QTY DESCRIPTION 1 GI 2000 G R D Unit 1 GI 2000 Flow Control Fitting 1 GI 2000 Ma...

Страница 4: ...osam Company has shipped the proper flow control fitting to suit the GRD that you have ordered Ensure that the proper flow control fitting is included with your shipment Changing the flow control fitt...

Страница 5: ...sure that there is 6 minimum clearance per side for latch removal Also provide a minimum of 24 on the outlet end in the event that the heating elements require service Provide adequate space on the in...

Страница 6: ...intake vent from flow control to outside opening and fit elbow turned down or intersect a common vent or vent stack without a trap as permitted by local codes Top of air intake from Flow Control is t...

Страница 7: ...5 DIAGRAM B Locate the installation diagram which most closely suits your requirement Install the flow control and GI 2000 as shown...

Страница 8: ...g Watts GFI Breaker 60306A 220 208 VAC 5000 Watts 25 AMP 60307A 220 208 VAC 7000 Watts 40 AMP 60308A 220 208 VAC 7000 Watts 40 AMP 60309A 220 208 VAC 7000 Watts 40 AMP 60310A 220 208 VAC 9000 Watts 50...

Страница 9: ...ng if removed is a M I P fitting Maximum head is 15 maintain connection Appropriate material should be used to accommodate possible temperatures of 140 F as well as vibrations when pumping When applic...

Страница 10: ...on addressing possible problems with the GI 2000 6 2 HEATER TEST 6 2 1 Open the controller door by loosening the front panel screws on the controller door 6 2 2 Press the TEST button once and the fol...

Страница 11: ...WITCH TEST 6 4 1 Open the controller door by loosening the front panel screws on the controller door 6 4 2 Press the TEST button once and the following message will be displayed PRESS UP OR DOWN KEYS...

Страница 12: ...sages will be displayed on the LCD Pressing UP will revert to the previous test Pressing DOWN will display the following message END OF TEST MODE PRESS ENTER TO EXIT 6 7 COMPLETION OF TESTING 6 7 1 To...

Страница 13: ...______ CONTACT Chas Tevis Phone 215 339 5370 Ext 212 Fax 800 962 3312 Date Power Mode Cycles Completed Water Level Cleaned Solids Reclaim Tank Status Initial Time Comments Ex Y Auto 0 1 1 2 4 3 Y Half...

Страница 14: ...he unit and tested at start up See Section 6 of Installation Section Should one of the values be determined to be invalid the unit will wait for the user to re enter the correct values 3 EXTERNAL CONT...

Страница 15: ...TO BEGIN CLEAN CYCLE 5 2 2 To initiate the manual clean cycle press the START button 5 3 PROCESS 5 3 1 Once the START button is pressed the clean cycle will begin the controller will beep and the foll...

Страница 16: ...call for maintenance 5 3 4 Once the preset temperature is reached the GI 2000 will pump the grease out and the following message will be displayed MANUAL CLEAN CYCLE IN PROGRESS PUMP ON XXXX TIME REM...

Страница 17: ...AN CYCLE 6 3 2 Without any action from the user the clean cycle will automatically begin The user may at this time or at any point in the clean cycle press the START STOP button to interrupt the cycle...

Страница 18: ...s intended to enter the date pump run time and calibrate the probe for measuring grease It is important to note that the probe calibration senses the water level in the tank Therefore the tank should...

Страница 19: ...ed to the Cal Mode menu 7 5 SETTING PROBE CALIBRATION 7 5 1 WHEN 7 5 1 1 To adjust the electronics for level of grease sensing It is important to remember that the sensor calibration senses the water...

Страница 20: ...ny water into the tank ensure that the tank is level and free of any grease or solids After filling the tank with water to level one of the calibration mark allow the water to settle and press ENTER t...

Страница 21: ...THREE times and the following message will be displayed PRESS UP DWN KEYS FOR DESIRED CAL PRESS ENTER TO SET PUMP ON TIME 7 6 2 After pressing ENTER the following message will be displayed USE UP AND...

Страница 22: ...9 will activate HIGH GREASE ALARM MORE OFTEN LOW Water Level Reading of 2 4 will activate HIGH GREASE ALARM MORE OFTEN MEDIUM Water Level Reading of 2 9 will activate HIGH GREASE ALARM MORE OFTEN HIGH...

Страница 23: ...TWARE VERSION 6 2 9 2 If the ENTER button is not pressed within 5 seconds the unit will revert to the automatic or manual mode If the ENTER button is pressed within the 5 seconds the following message...

Страница 24: ...ater Level Test Reading should be between 1 0 3 5 a Calibration See section 7 pages 16 19 of a manual b Notify factory for assistance Difficulty in calibrating unit Poor Connection to Probe 1 Verify c...

Страница 25: ...OVERY DEVICE Location of unit to source Check to insure that unit is level Check for proper orientation Check for proper electrical connection Check baffles Check for proper connection to GI 2000 Cont...

Отзывы: