45
2.11 Simplified electronic controller wiring diagram
Dip-switch 1 must always be set to ON
To control the lighting of a boiler connected in parallel, set
dip-switch 3 to ON
To control the gear motor of the supplementary pellet
hopper, set dip-switch 3 to OFF
To control the thermoboiler for hot water tank, set dip-
switch 4 to OFF
To control the heating chamber, set dip-switch 4 to ON
DIP-SWITCH POSITION
AIR
WATER
Boiler air temperature probe
Fume temperature probe
Room temp. probe
or room thermostat (optional)
Supplementary pellet hopper
motor
Fuse (6.3A)
230V 50Hz line
Control panel
Ambient Air fan
Ignition electrical
element
Safety
thermostat
Pellet
gear motor
Connector
Pellet level sensor
on standard pellet hopper
Combustion air fan
Supplementary pellet hopper
(see “Auger or pneumatic conveyance
assembly card”)
Electrical connections must be carried out by skilled personnel according to the regulations in force (CE 2006/95 and 2004/108).
The representation of the components is only indicative, these can be changed in form.
LOW
level
sensor
Connector
Connector
T
erminals unit
”Ground Commutator”
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
1
ON Room thermostat probe
OFF XXXXXX
2
ON Air heating model
OFF Water heating model
3
ON Relay for external boiler in parallel
OFF Relay for supplementary pellet hopper motor
4
ON Heating chamber
(optional probe)
OFF DHW thermoboiler
(optional probe)
5
ON Buffer battery active
OFF Buffer battery excluded
Pressure switch
1
2
3
Pressure switch connections
Connect the cables to the
appropriate terminals:
BLACK wire to terminal 1
C
BROWN wire to terminal 2
NC
BLUE wire to terminal 3
NO