The table below shows the minimum, maximum and default values:
The table below details the real time error numbers and a description of each error:
1
-
43
Form 201.26.OI1(11/09)
DESCRIPTION
MINIMUM
MAXIMUM
DEFAULT
De Modifier Address
-1
41943
-1
De Modifier Offset
-1
99
-1
BACNET
API
BACNET
P1 Manual Mac Address
0
127
1
1200
76800
4800
None
Ignore
None
P1 Stop Bits
1
2
1
Terminal
Modbus Client
API
P2 Manual Mac Address
0
127
1
1200
76800
1200
None
Ignore
None
P2 Stop Bits
1
2
1
P2 HW Select Bit
RS232
RS485
RS232
Reset Real Time Error
NO
YES
None
P2 Baud Rate
P2 Parity
None, Even, Odd, Ignore Selectable
None, Even, Odd, Ignore Selectable
P2 Protocol
TERMINAL, UNAVAIL, MODBUS IO, MODBUS SERVER, API, MODBUS CLIENT Selectable
P1 Parity
1200, 4800, 9600, 19200, 38400, 57600, 76800 Selectable
P1 Protocol
BACNET, API Selectable
P1 Baud Rate
1200, 4800, 9600, 19200, 38400, 57600, 76800 AUTO Selectable
ERROR NUMBER
(##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED