Care and 

Maintenance

The TYCO Model RFII HSW Concealed 

Sprinkler must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION, such as NFPA 25, in 

addition to the standards of any other 

authorities having jurisdiction.  Contact 

the installing contractor or product 

manufacture with any questions.
Automatic sprinkler systems should be 

inspected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.
When properly installed, there is a 

nominal 5/32 in. (4,0 mm) air gap 

between the lip of the Cover Plate and 

the wall, as shown in Figure 3. This 

air gap is necessary for proper oper-

ation of the sprinkler. If the wall is to 

be repainted after the installation of 

the sprinkler, care must be exercised 

to ensure that the new paint does not 

seal off any of the air gap.
Factory painted cover plates must not 

be repainted. They should be replaced 

if necessary, by factory painted units.  

Non-factory applied paints may 

adversely delay or prevent sprinkler 

operation in the event of a fire.

If removal of the Cover Plate is neces-

sary relative to the Enclosure, be con-

scious not to be too forceful, where 

separation may result.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated or otherwise 

altered after leaving the factory.  Modi-

fied or over heated sprinklers must be 

replaced.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced.
If a sprinkler must be removed, do not 

reinstall it or a replacement without 

reinstalling the Cover Plate Assembly.  

If a Cover Plate Assembly becomes 

dislodged during service, replace it 

immediately.

Содержание tyco RFII

Страница 1: ... form a complete assembly The separable two piece design of the sprinkler provides for 1 4 in 6 4 mm horizontal adjustment of the push on and pull off cover plate With sprinklers installed but before cover plates are attached pressure testing of the fire protection system may be performed prior to completing wall assemblies such as installation of gypsum board over stud framing and surface finish ...

Страница 2: ...e UL Listed for Light and Ordinary Hazard Occupancies at a 4 to 12 in 100mm to 300mm top of deflector to ceiling distance 1 Body 6 Deflector Guide Pin 11 Plug 16 Retainer 2 1 2 in NPT 7 Frame 12 Lever 17 Retainer Friction Grip 3 Wrenching Notch 8 Button 13 Compression Screw 18 Cover Plate Solder Tab 4 Sprinkler Waterway 9 Sealing Assembly 14 Link 19 Cover Plate 5 Deflector 10 Bridge 15 Protective ...

Страница 3: ...rench contains an outer flat surface reference that correlates with the sprinkler deflec tor orientation The word UP on the installation wrench is to face towards the ceiling to ensure proper alignment as shown in Figure 4 NOTICE Do not remove the Protective Cap shown in Figure 1 until the Cover Plate Assembly is installed and or the fire protection sprinkler system is ready to be placed in servic...

Страница 4: ...f it becomes necessary to remove the Cover Plate it can be removed merely by gently pulling the Cover Plate Assembly away from the sprin kler body Note A Cover Plate Assembly not ade quately engaging the sprinkler body that is not securely attached indicates the sprinkler is positioned at a distance from the mounting surface greater than is described in Figure 3 A Cover Plate Assembly fully engage...

Страница 5: ...between the lip of the Cover Plate and the wall as shown in Figure 3 This air gap is necessary for proper oper ation of the sprinkler If the wall is to be repainted after the installation of the sprinkler care must be exercised to ensure that the new paint does not seal off any of the air gap Factory painted cover plates must not be repainted They should be replaced if necessary by factory painted...

Страница 6: ...rin kler Cover Plate Assembly tempera ture rating specify specify finish P N specify 139 F 59 C Ivory RAL1015 56 204 0 135 Beige RAL1001 56 204 2 135 Pure White RAL9010 56 204 3 135 Signal White RAL9003 56 204 4 135 Grey White RAL9002 56 204 5 135 Brown RAL8028 56 204 6 135 Black RAL9005 56 204 7 135 Brushed Brass 56 204 8 135 Brushed Chrome 56 204 9 135 Custom Paint 56 204 X 135 165 F 74 C Ivory ...

Отзывы: