TFP185

Page 3 of 6

Operation

When exposed to heat from a fire, the 

Cover Plate, which is soldered to the 

Retainer Ring at three points, falls away 

to expose the Sprinkler Assembly, as 

shown in Figure 2. The link’s solder 

melts when exposed to heat. When 

the rated temperature is reached, the 

melted solder releases the link, activat-

ing the sprinkler and allowing water to 

flow.

Design 

Criteria

The TYCO Model RFII HSW Concealed 

Sprinkler is UL and C-UL Listed for use 

in ordinary and light hazard occupan-

cies, using the requirements specified 

in the current NFPA 13 for standard 

coverage sidewall sprinklers.

Installation

The TYCO Model RFII HSW Concealed 

Sprinkler must be installed in accor-

dance with this section.
A ½ in. (12,7 mm) NPT sprinkler joint 

should be obtained with a minimum 

to maximum torque of 10 to 20 lb-ft 

(13,6 to 27,1 N·m). Higher levels of 

torque may distort the sprinkler with 

consequent leakage or impairment of 

the sprinkler. Do not attempt to com-

pensate for insufficient adjustment in 

the Sprinkler Assembly by under-or 

over-tightening the sprinkler. Readjust 

the position of the sprinkler fitting to 

suit.

Step 1.

 The sprinkler must only be 

installed with its centerline perpen-

dicular to the back wall and parallel to 

the ceiling. Use a W-Type 37 Wrench 

for installation. The wrench contains 

an outer flat surface reference that 

correlates with the sprinkler deflec-

tor orientation. The word “UP” on the 

installation wrench is to face towards 

the ceiling to ensure proper alignment, 

as shown in Figure 4.

NOTICE

Do not remove the Protective Cap, 

shown in Figure 1, until the Cover Plate 

Assembly is installed and/or the fire 

protection sprinkler system is ready to 

be placed in service.

Step 2.

 With pipe thread sealant 

applied to the sprinkler threads, and 

ensuring that no pipe thread sealant 

is in contact with the Deflector Guide 

Pins, align the sprinkler alignment slot 

with the W-Type 37 Sprinkler Wrench 

*

*

FACE OF

SPRINKLER

FITTING

SPRINKLER

ASSEMBLY

WRENCHING

NOTCHES

NOTICE

Factory-assembled protective cap

to remain attached during sprinkler

installation; Temporarily remove to

verify proper deflector orientation

and reinstall during wall finishing;

Remove only after installation is

complete to allow proper sprinkler

performance; LDPE cap may be

recycled accordingly

PROTECTIVE

CAP

CENTERLINE

OF SPRINKLER

WATERWAY

MOUNTING

SURFACE

TOP OF

DEFLECTOR

CAP FULLY

SEATED ON

SPRINKLER

WRENCHING

FLANGE

2-5/8" DIA.

(66,7 mm)

CLEARANCE

HOLE

3-3/16" DIA.

(81,0 mm)

RETAINER

COVER

PLATE

3/16"

(4,8 mm)

WALL

CENTER

MARKING

TIP

RETAINER FLANGE

FLUSH AGAINST

MOUNTING SURFACE

5/32" GAP

(4,0 mm)

SPRINKLER

BODY ENGAGED

BY RETAINER

FRICTION GRIPS

COVER PLATE

ASSEMBLY

1/4" (6,4 mm)

ADJUSTMENT

1-9/16" ± 1/8"

(39,7 mm ± 3,2 mm)

9/16"

(14,3 mm)

FIGURE 3 

MODEL RFII HSW CONCEALED SPRINKLER 

INSTALLATION CRITERIA

Содержание tyco RFII

Страница 1: ... form a complete assembly The separable two piece design of the sprinkler provides for 1 4 in 6 4 mm horizontal adjustment of the push on and pull off cover plate With sprinklers installed but before cover plates are attached pressure testing of the fire protection system may be performed prior to completing wall assemblies such as installation of gypsum board over stud framing and surface finish ...

Страница 2: ...e UL Listed for Light and Ordinary Hazard Occupancies at a 4 to 12 in 100mm to 300mm top of deflector to ceiling distance 1 Body 6 Deflector Guide Pin 11 Plug 16 Retainer 2 1 2 in NPT 7 Frame 12 Lever 17 Retainer Friction Grip 3 Wrenching Notch 8 Button 13 Compression Screw 18 Cover Plate Solder Tab 4 Sprinkler Waterway 9 Sealing Assembly 14 Link 19 Cover Plate 5 Deflector 10 Bridge 15 Protective ...

Страница 3: ...rench contains an outer flat surface reference that correlates with the sprinkler deflec tor orientation The word UP on the installation wrench is to face towards the ceiling to ensure proper alignment as shown in Figure 4 NOTICE Do not remove the Protective Cap shown in Figure 1 until the Cover Plate Assembly is installed and or the fire protection sprinkler system is ready to be placed in servic...

Страница 4: ...f it becomes necessary to remove the Cover Plate it can be removed merely by gently pulling the Cover Plate Assembly away from the sprin kler body Note A Cover Plate Assembly not ade quately engaging the sprinkler body that is not securely attached indicates the sprinkler is positioned at a distance from the mounting surface greater than is described in Figure 3 A Cover Plate Assembly fully engage...

Страница 5: ...between the lip of the Cover Plate and the wall as shown in Figure 3 This air gap is necessary for proper oper ation of the sprinkler If the wall is to be repainted after the installation of the sprinkler care must be exercised to ensure that the new paint does not seal off any of the air gap Factory painted cover plates must not be repainted They should be replaced if necessary by factory painted...

Страница 6: ...rin kler Cover Plate Assembly tempera ture rating specify specify finish P N specify 139 F 59 C Ivory RAL1015 56 204 0 135 Beige RAL1001 56 204 2 135 Pure White RAL9010 56 204 3 135 Signal White RAL9003 56 204 4 135 Grey White RAL9002 56 204 5 135 Brown RAL8028 56 204 6 135 Black RAL9005 56 204 7 135 Brushed Brass 56 204 8 135 Brushed Chrome 56 204 9 135 Custom Paint 56 204 X 135 165 F 74 C Ivory ...

Отзывы: