background image

TFP185

Page 4 of 6

alignment slot, as shown in Figure 4. 

Engage by inserting the sprinkler into 

the wrench cavity, fully seating the 

wrench shoulder against the sprinkler 

wrenching flange. Hand tighten the 

sprinkler into the sprinkler fitting.

Step 3. 

Once hand tight, attach ½ in. 

(12,7 mm) drive to the sprinkler wrench, 

as shown in Figure 4. Wrench-tighten 

to ensure proper seal and alignment, 

taking care to ensure the Deflector 

Guide Pins do not come in contact with 

any foreign body or surface.

Step 4.

 After the wall has been com-

pleted with the nominal 2-5/8 in. 

(66,7 mm) diameter clearance hole and 

in preparation for installing the Cover 

Plate Assembly, remove and discard 

the Protective Cap. If the sprinkler has 

been damaged in any way including 

accidental over spray from finishing the 

wall, replace the entire sprinkler.

NOTICE

The sprinkler must be installed in the  

neutral or negative plenum only.

Step 5.

 Push the Cover Plate Assem-

bly onto the Sprinkler, and as neces-

sary, make the final adjustment of the 

Cover Plate with respect to the wall by 

pushing the Cover Plate Assembly until 

the retainer flange is flush against the 

wall. If it becomes necessary to remove 

the Cover Plate, it can be removed 

merely by gently pulling the Cover 

Plate Assembly away from the sprin-

kler body.

Note:

 A Cover Plate Assembly not ade-

quately engaging the sprinkler body, 

that is not securely attached, indicates 

the sprinkler is positioned at a distance 

from the mounting surface greater than 

is described in Figure 3. A Cover Plate 

Assembly fully engaged on the sprin-

kler body while the retainer flange is 

not in contact with the wall indicates 

the sprinkler is positioned at a distance 

from the mounting surface lesser than 

described in Figure 3. If either condi-

tion is encountered when attempting 

to install the Cover Plate Assembly, the 

sprinkler fitting must be repositioned.

SPRINKLER

FITTING

WRENCHING

NOTCH

PROTECTIVE

CAP

PROTECTIVE

CAP

WRENCH

KEY

RFII

SPRINKLER

W-TYPE 37

SPRINKLER

WRENCH

WRENCH

CAVITY

SOCKET

ACCEPTS

1/2" DRIVE

WRENCH

ALIGNMENT

SLOT READILY

ORIENTS WRENCH

WITH SPRINKLER

ALIGNMENT

SLOT

THREE

WRENCH

KEYS

UNIQUELY

SPACED TO

ENGAGE

SPRINKLER

WRENCHING

NOTCHES

"UP" INDICATES

TOP OF

DEFLECTOR

WRENCH

ALIGNMENT

SLOT

SPRINKLER

ALIGNMENT

SLOT

WRENCH

SHOULDER

SPRINKLER

WRENCHING

FLANGE

WRENCH

SHOULDER

SEATED ON

SPRINKLER

WRENCHING

FLANGE

WRENCH FLAT

ACCOMMODATES

LEVEL FOR PRECISE

ADJUSTMENT TO

DEFLECTOR

ORIENTATION

AS NEEDED

FIGURE 4 

W-TYPE 37 SPRINKLER  

WRENCH

Содержание tyco RFII

Страница 1: ... form a complete assembly The separable two piece design of the sprinkler provides for 1 4 in 6 4 mm horizontal adjustment of the push on and pull off cover plate With sprinklers installed but before cover plates are attached pressure testing of the fire protection system may be performed prior to completing wall assemblies such as installation of gypsum board over stud framing and surface finish ...

Страница 2: ...e UL Listed for Light and Ordinary Hazard Occupancies at a 4 to 12 in 100mm to 300mm top of deflector to ceiling distance 1 Body 6 Deflector Guide Pin 11 Plug 16 Retainer 2 1 2 in NPT 7 Frame 12 Lever 17 Retainer Friction Grip 3 Wrenching Notch 8 Button 13 Compression Screw 18 Cover Plate Solder Tab 4 Sprinkler Waterway 9 Sealing Assembly 14 Link 19 Cover Plate 5 Deflector 10 Bridge 15 Protective ...

Страница 3: ...rench contains an outer flat surface reference that correlates with the sprinkler deflec tor orientation The word UP on the installation wrench is to face towards the ceiling to ensure proper alignment as shown in Figure 4 NOTICE Do not remove the Protective Cap shown in Figure 1 until the Cover Plate Assembly is installed and or the fire protection sprinkler system is ready to be placed in servic...

Страница 4: ...f it becomes necessary to remove the Cover Plate it can be removed merely by gently pulling the Cover Plate Assembly away from the sprin kler body Note A Cover Plate Assembly not ade quately engaging the sprinkler body that is not securely attached indicates the sprinkler is positioned at a distance from the mounting surface greater than is described in Figure 3 A Cover Plate Assembly fully engage...

Страница 5: ...between the lip of the Cover Plate and the wall as shown in Figure 3 This air gap is necessary for proper oper ation of the sprinkler If the wall is to be repainted after the installation of the sprinkler care must be exercised to ensure that the new paint does not seal off any of the air gap Factory painted cover plates must not be repainted They should be replaced if necessary by factory painted...

Страница 6: ...rin kler Cover Plate Assembly tempera ture rating specify specify finish P N specify 139 F 59 C Ivory RAL1015 56 204 0 135 Beige RAL1001 56 204 2 135 Pure White RAL9010 56 204 3 135 Signal White RAL9003 56 204 4 135 Grey White RAL9002 56 204 5 135 Brown RAL8028 56 204 6 135 Black RAL9005 56 204 7 135 Brushed Brass 56 204 8 135 Brushed Chrome 56 204 9 135 Custom Paint 56 204 X 135 165 F 74 C Ivory ...

Отзывы: