TFP185

Page 2 of 6

Maximum Working Pressure

250 psi (17,2 bar)

Discharge Coefficient 

K=5.6 gpm/psi

½

 (80,6 lpm/bar

½

)

Temperature Rating

160°F (71°C) Sprinkler with 

139°F (59°C) Cover Plate
212°F (100°C) Sprinkler with 

165°F (74°C) Cover Plate

Horizontal Adjustment

¼ in. (6,4 mm)

Finishes

See the Ordering Procedure section

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 

Bridge . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Soldered Link Halves . . . . . . . . . . . . . . . .  Nickel

Compression Screw . . . . . . . . . .  Stainless Steel

Deflector Guide Pins . . . . . . . . . .  Stainless Steel

Plug  . . . . . . . . . . . . . . . . . . . . . . . . . Polyethylene

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Retainer . . . . . . . . . . . . . . . . Copper Plated Steel

Cover Plate . . . . . . . . . . . . . . . . . . . . . . .  Copper

Cover Plate Ejection Spring . . . .  Stainless Steel

Note: 

UL Listed for Light and Ordinary Hazard Occupancies at a  
4 to 12 in. (100mm to 300mm) top of deflector-to-ceiling distance.

1 – Body

6 – Deflector Guide Pin

11 – Plug

16 – Retainer

2 – 1/2 in. NPT

7 – Frame

12 – Lever

17 – Retainer Friction Grip

3 – Wrenching Notch

8 – Button

13 – Compression Screw

18 – Cover Plate Solder Tab

4 – Sprinkler Waterway

9 – Sealing Assembly

14 – Link

19 – Cover Plate

5 – Deflector

10 – Bridge

15 – Protective Cap

20 – Cover Plate Ejection Spring

SPRINKLER

ASSEMBLY

COVER PLATE

ASSEMBLY

1

4

9

2

3

8

7

6

15

13

14

11

10

12

5

19

16

17

18

20

CENTERLINE

OF SPRINKLER

WATERWAY

MOUNTING

SURFACE

TOP OF

DEFLECTOR

OPERATED

COVER PLATE

ASSEMBLY

OPERATED

SPRINKLER

DEFLECTOR

IN OPERATED

POSITION

9/16"

(14,3 mm)

7/16" (11,3 mm) MIN.

11/16" (17,5 mm) MAX.

FIGURE 1 

MODEL RFII HSW CONCEALED SPRINKLER 

ASSEMBLY AND FEATURES

FIGURE 2 

MODEL RFII HSW CONCEALED SPRINKLER 

OPERTATED CONDITION

Содержание tyco RFII

Страница 1: ... form a complete assembly The separable two piece design of the sprinkler provides for 1 4 in 6 4 mm horizontal adjustment of the push on and pull off cover plate With sprinklers installed but before cover plates are attached pressure testing of the fire protection system may be performed prior to completing wall assemblies such as installation of gypsum board over stud framing and surface finish ...

Страница 2: ...e UL Listed for Light and Ordinary Hazard Occupancies at a 4 to 12 in 100mm to 300mm top of deflector to ceiling distance 1 Body 6 Deflector Guide Pin 11 Plug 16 Retainer 2 1 2 in NPT 7 Frame 12 Lever 17 Retainer Friction Grip 3 Wrenching Notch 8 Button 13 Compression Screw 18 Cover Plate Solder Tab 4 Sprinkler Waterway 9 Sealing Assembly 14 Link 19 Cover Plate 5 Deflector 10 Bridge 15 Protective ...

Страница 3: ...rench contains an outer flat surface reference that correlates with the sprinkler deflec tor orientation The word UP on the installation wrench is to face towards the ceiling to ensure proper alignment as shown in Figure 4 NOTICE Do not remove the Protective Cap shown in Figure 1 until the Cover Plate Assembly is installed and or the fire protection sprinkler system is ready to be placed in servic...

Страница 4: ...f it becomes necessary to remove the Cover Plate it can be removed merely by gently pulling the Cover Plate Assembly away from the sprin kler body Note A Cover Plate Assembly not ade quately engaging the sprinkler body that is not securely attached indicates the sprinkler is positioned at a distance from the mounting surface greater than is described in Figure 3 A Cover Plate Assembly fully engage...

Страница 5: ...between the lip of the Cover Plate and the wall as shown in Figure 3 This air gap is necessary for proper oper ation of the sprinkler If the wall is to be repainted after the installation of the sprinkler care must be exercised to ensure that the new paint does not seal off any of the air gap Factory painted cover plates must not be repainted They should be replaced if necessary by factory painted...

Страница 6: ...rin kler Cover Plate Assembly tempera ture rating specify specify finish P N specify 139 F 59 C Ivory RAL1015 56 204 0 135 Beige RAL1001 56 204 2 135 Pure White RAL9010 56 204 3 135 Signal White RAL9003 56 204 4 135 Grey White RAL9002 56 204 5 135 Brown RAL8028 56 204 6 135 Black RAL9005 56 204 7 135 Brushed Brass 56 204 8 135 Brushed Chrome 56 204 9 135 Custom Paint 56 204 X 135 165 F 74 C Ivory ...

Отзывы: