Page 7 of 8

Installation

The Model CC1 Sprinklers must be 

installed in accordance with this 

section.

General Instructions

The Model CC1 Sprinklers are to be 

installed upright and with their frame 

arms (Ref. Figure 1) parallel with the 

wood trusses, top chord of the bar joist, 

or wood joists, as opposed to being 

necessarily parallel with the pipe (Ref. 

Figures 2 through 7 as applicable).
Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm) for the 175°F (79°C) tempera-

ture rating.
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained with a torque of 7 to 

14 lb-ft (9,5 to 19,0 N

m). Higher levels 

of torque may distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
The Model CC1 Sprinklers must only 

be installed in the upright position with 

the deflector parallel to the upper deck. 

With pipe thread sealant applied to the 

pipe threads, use only the W-Type 20 

(End B) Sprinkler Wrench (Ref. Figure 

9) for installation of the Model CC1 

Sprinklers by applying the wrench to 

the sprinkler wrench flats only.

0"

2-1/2"

(63,5 mm)

3-1/2"

(88,9 mm)

5-1/2"

(139,7 mm)

7-1/2"

(190,5 mm)

9-1/2"

(241,3 mm)

12"

(304,8 mm)

14"

(355,6 mm)

16-1/2"

(419,1 mm)

(0 mm)

Maximum Allowable

Distance of Deflector

Above Bottom of

Obstruction

(B)

Distance from

Centerline of

Sprinkler to Side

of Obstruction

(A)

A≥3C or 3D

A≤24" (609,6 mm)

(Use dimension C or D, whichever is greater)

<12"
<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
18" to <24"

(457,2 mm to <609,6 mm)
24" to <30"

(609,6 mm to <762,0 mm)
30" to <36"

(762,0 mm to <914,4 mm)
36" to <42"

(914,4 mm to <1066,8 mm)
42" to <48"

(1066,8 mm to <1219,2 mm)
48" to <54"

(1219,2 mm to <1371,6 mm)
54" to <60"

(1371,6 mm to <1524,0 mm)

NOTE:
WEB MEMBERS AND GUSSETS

SHALL NOT BE CONSIDERED

OBSTRUCTIONS PROVIDED THE

MINIMUM 4-1/2 INCH LATERAL

DISTANCE (FIG. 2) REQUIRED

BY THE SPECIFIC APPLICATION

LISTING IS MAINTAINED.

OBSTRUCTION

MODEL CC1

SPRINKLER

C

D

A

OBSTRUCTION

UPPER

DECK

LOWER

DECK

A

MODEL CC1

SPRINKLER

MODEL CC1

SPRINKLER

A

UPPER DECK

OR BOTTOM OF

NON-COMUSTIBLE

INSULATION

B

ELEVATION VIEW

PLAN VIEW

C

D

OBSTRUCTION

WRENCH RECESS

(USE END "B" FOR

MODEL CC1)

FIGURE 8 

NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA 

(REFERENCE)

FIGURE 9 

W-TYPE 20 

SPRINKLER WRENCH

Содержание tyco CC1

Страница 1: ...this product Concealed spaces between floors as well as low pitch attics are inherently shallow Standard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challeng...

Страница 2: ...R CPVC that is offset over an obstruction Required Density CPVC Pipe 0 10 gpm ft 4 1 mm min Minimum Operating Pressure CPVC Pipe 10 psi 0 7 bar Obstructions CPVC Pipe All obstruction criteria per NFPA...

Страница 3: ...SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE PIPE RUN OBSTRUCTION CEILING MODEL CC1 SPRINKLER UPPER DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 2 51 mm MAXIMUM 6...

Страница 4: ...ay be constructed of 1 4 in 6 4 mm plywood to prevent heat from escaping beyond the area For non combustible insulation filled solid wood joist or composite wood joist construction Ref Figure 6 the re...

Страница 5: ...ITH PIPE RUN CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6...

Страница 6: ...15 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH TRUSSES NOT NECESSARILY WITH PIPE RUN UPPER DECK MODEL CC1 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER...

Страница 7: ...the W Type 20 End B Sprinkler Wrench Ref Figure 9 for installation of the Model CC1 Sprinklers by applying the wrench to the sprinkler wrench flats only 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7...

Страница 8: ...cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers dama...

Отзывы: