background image

TFP630

Page 4 of 8

Design Criteria, 

Steel Pipe

Area of Use (Steel Pipe)

Horizontal (slope not exceeding 2 in 12) 

combustible concealed spaces of:
•  wood truss construction or bar joist 

construction (Ref. Figure 4)

•  solid wood joist construction (Ref. 

Figure 5) where the upper deck and 

ceiling joists may have a maximum 

depth of 12 in. (300 mm) and typical 

on center joist spacing of minimum 

16 in. (400 mm)

•  non-combustible insulation filled 

solid wood joist or wood composite 

joist construction (Ref. Figure 6)

NOTE:

 In order to be considered “non-

combustible insulation filled solid wood 

joist or composite wood joist con-

struction”, the insulation (including 

insulation provided with a combusti-

ble vapor barrier), must completely fill 

the pockets between the joists to the 

bottom of the joists, and the insulation 

must be secured in place with metal 

wire netting. The metal wire netting is 

intended to hold the insulation in place 

should the insulation become wetted 

by the operation of the CC1 Sprinklers 

in the event of a fire.

Concealed Space Area (Steel Pipe)

The area of the concealed space is not 

limited; however:
•  for wood truss construction or con-

cealed spaces of non-combustible 

bar joist construction (Ref. Figure 

4) draft-curtains or full height walls 

must be provided at 1000 ft² (93 m²) 

areas. This draft curtain shall be at 

least 1/3 the depth of the concealed 

space or 8 in. (200 mm), whichever 

is greater, and be constructed using 

a material which will not allow heat 

to escape through or above the draft 

curtain.

•  for solid wood joist construction 

(Ref. Figure 5), blocking must be pro-

vided in each upper deck and ceil-

ing joist channel at a maximum 32 ft  

(9,75 m) intervals. This blocking 

shall be installed to the full depth 

of the joists and be installed so as 

to not allow heat to escape through 

or above the blocking. The blocking 

must be constructed using a non-

combustible material or the joist con-

struction material.
Solid wall construction or draft cur-

tains must protrude below the joist 

a minimum of 6 in. (150 mm) or 

1/3 the space, whichever is small-

est and  run laterally with the joist 

spaced at 25 ft (7,6 m) width maxi-

mum to limit the area to a maximum 

of 1000 ft² (93 m²). The draft curtain 

may be constructed of 1/4 in. 

(6,4 mm) plywood to prevent heat 

from escaping beyond the area.

•  For non-combustible insulation filled 

solid wood joist or composite wood 

joist construction (Ref. Figure 6), 

the requirement for draft curtains or 

blocking does not apply.

Concealed Space Size (Steel Pipe)

The minimum and maximum concealed 

space depth is as follows:
For wood truss construction or con-

cealed spaces of non-combustible bar 

joist construction (Ref. Figure 4) the 

depth of the concealed space is 36 in. 

(915 mm) maximum to 12 in. (305 mm) 

minimum.
For solid wood joist construction (Ref. 

Figure 5) or for non-combustible insu-

lation filled solid wood or composite 

wood joist construction (Ref. Figure 6), 

the  maximum depth of the concealed 

space is 54 in. (1372 mm) from bottom 

of upper deck to top of ceiling, and the 

minimum depth is 6 in. (150 mm) from 

the bottom of the upper deck joists to 

the top of the ceiling joists.
For obstructed wood truss construc-

tion (Ref. Figure 7), the maximum depth 

of the concealed space is 54 in. (1372 

mm) from bottom of upper deck to top 

of ceiling, and the minimum depth is 

6 in. (152 mm) from the bottom of the 

upper chord to the top of the lower 

chord.

System Type (Steel Pipe)

Light hazard, wet pipe system

Minimum Distance Between Model 

CC1 Sprinklers (Steel Pipe)

6 ft (1,8 m)

Maximum Distance Between Model 

CC1 Sprinklers (Steel Pipe)

10 ft (3,1 m)

Maximum Coverage Area 

(Steel Pipe)

100 ft² (9,3 m²)

Deflector Position (Steel Pipe)

1-1/2 in. to 4 in. (40 to 100 mm) below 

upper deck for wood truss construction 

or concealed spaces of non-combusti-

ble bar joist construction (Ref. Figure 4)
1-1/2 in. to 2 in. (40 to 50 mm) below 

solid wood joists (Ref. Figure 5)
1-1/2 in. to 2 in. (40 to 50 mm) below 

non-combustible insulation filled solid 

wood joists or composite wood joists 

(Ref. Figure 6)

Remote Area (Steel Pipe)

The remote area for wood truss con-

struction or bar joist construction (Ref. 

Figure 4) or solid wood joist construc-

tion (Ref. Figure 5) is 1000 ft² (93 m²).
The remote area for non-combusti-

ble insulation filled solid wood joist 

or wood composite joist construction 

(Ref. Figure 6) is to be calculated per 

the requirements of NFPA 13.

Required Density (Steel Pipe)

0.10 gpm/ft² (4,1 mm/min)

Minimum Operating Pressure 

(Steel Pipe)

10 psi (0,7 bar)

Obstructions (Steel Pipe)

All obstruction criteria per NFPA for 

standard spray sprinklers apply (Ref. 

Figure 8), unless modified by this tech-

nical data sheet.

Содержание tyco CC1

Страница 1: ...this product Concealed spaces between floors as well as low pitch attics are inherently shallow Standard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challeng...

Страница 2: ...R CPVC that is offset over an obstruction Required Density CPVC Pipe 0 10 gpm ft 4 1 mm min Minimum Operating Pressure CPVC Pipe 10 psi 0 7 bar Obstructions CPVC Pipe All obstruction criteria per NFPA...

Страница 3: ...SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE PIPE RUN OBSTRUCTION CEILING MODEL CC1 SPRINKLER UPPER DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 2 51 mm MAXIMUM 6...

Страница 4: ...ay be constructed of 1 4 in 6 4 mm plywood to prevent heat from escaping beyond the area For non combustible insulation filled solid wood joist or composite wood joist construction Ref Figure 6 the re...

Страница 5: ...ITH PIPE RUN CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6...

Страница 6: ...15 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH TRUSSES NOT NECESSARILY WITH PIPE RUN UPPER DECK MODEL CC1 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER...

Страница 7: ...the W Type 20 End B Sprinkler Wrench Ref Figure 9 for installation of the Model CC1 Sprinklers by applying the wrench to the sprinkler wrench flats only 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7...

Страница 8: ...cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers dama...

Отзывы: