background image

TFP630

Page 6 of 8

FRAME ARMS OF SPRINKLER MUST BE

INSTALLED PARALLEL WITH JOISTS,

NOT NECESSARILY WITH PIPE RUN

UPPER

DECK

MODEL CC1

SPRINKLER

CEILING

FRAMING

2x FLOOR SOLID

WOOD JOISTS

NON-COMBUSTIBLE

INSULATION

COMPOSITE

WOOD JOISTS

1-1/2" (38 mm)

MINIMUM

CEILING

4" (102 mm)

MAXIMUM

54" (1372 mm)

MAXIMUM

6" (152 mm)

MINIMUM

36" (915 mm)

MAXIMUM

FRAME ARMS OF SPRINKLER MUST BE

INSTALLED PARALLEL WITH TRUSSES,

NOT NECESSARILY WITH PIPE RUN

UPPER

DECK

MODEL CC1

SPRINKLER

CEILING

FRAMING

54" (1372 mm)

MAXIMUM

CEILING

TOP CHORD GREATER

THAN 4" (102 mm) IN DEPTH

6" (152 mm)

MINIMUM

36" (915 mm)

MAXIMUM

1-1/2" (38 mm)

MINIMUM

2" (51 mm)

MAXIMUM

FIGURE 7 

OBSTRUCTED WOOD TRUSS CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

FIGURE 6 

NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK 

 SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

Содержание tyco CC1

Страница 1: ...this product Concealed spaces between floors as well as low pitch attics are inherently shallow Standard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challeng...

Страница 2: ...R CPVC that is offset over an obstruction Required Density CPVC Pipe 0 10 gpm ft 4 1 mm min Minimum Operating Pressure CPVC Pipe 10 psi 0 7 bar Obstructions CPVC Pipe All obstruction criteria per NFPA...

Страница 3: ...SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE PIPE RUN OBSTRUCTION CEILING MODEL CC1 SPRINKLER UPPER DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 2 51 mm MAXIMUM 6...

Страница 4: ...ay be constructed of 1 4 in 6 4 mm plywood to prevent heat from escaping beyond the area For non combustible insulation filled solid wood joist or composite wood joist construction Ref Figure 6 the re...

Страница 5: ...ITH PIPE RUN CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6...

Страница 6: ...15 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH TRUSSES NOT NECESSARILY WITH PIPE RUN UPPER DECK MODEL CC1 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER...

Страница 7: ...the W Type 20 End B Sprinkler Wrench Ref Figure 9 for installation of the Model CC1 Sprinklers by applying the wrench to the sprinkler wrench flats only 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7...

Страница 8: ...cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers dama...