TFP630

Page 2 of 8

Design Criteria, 

CPVC Pipe

Area of Use (CPVC Pipe)

Horizontal (slope not exceeding 2 in 12) 

combustible concealed spaces of:
•  Wood truss construction or bar joist 

construction (Ref. Figure 2)

•  Non-combustible insulation filled 

solid wood or composite wood joist 

construction (Ref. Figure 3)

NOTE:

 In order to be considered 

“non-combustible insulation filled 

solid wood or composite wood joist 

construction”, the insulation (includ-

ing insulation provided with a combus-

tible vapor barrier), must completely fill 

the pockets between the joists to the 

bottom of the joists, and the insulation 

must be secured in place with metal 

wire netting. The metal wire netting is 

intended to hold the insulation in place 

should the insulation become wetted 

by the operation of the CC1 Sprinklers 

in the event of a fire.

Concealed Space Area (CPVC Pipe)

The area of the concealed space is not 

limited; however, for both Figure 2 and 

Figure 3, where CPVC pipe is being uti-

lized, draft-curtains or full height walls 

must be provided at 1000 ft² (93 m²) 

areas. This  draft curtain shall be at 

least 1/3 the depth of the concealed 

space or 8 in. (200 mm), whichever  is  

greater,  and  be  constructed using 

a material which will not allow heat 

to escape through or above the draft 

curtain.

Concealed Space Size (CPVC Pipe)

The depth of the concealed space is 

36 in. (915 mm) maximum to 12 in.  

(305 mm) minimum.

System Type (CPVC Pipe)

Light hazard, wet pipe system

Minimum Distance Between Model 

CC1 Sprinklers (CPVC Pipe)

6 ft (3,1 m). Minimum spacing does 

not apply to any additional sprinklers 

required for protection of BLAZE-

MASTER CPVC that is offset over an 

obstruction.

Maximum Distance Between Model 

CC1 Sprinklers (CPVC Pipe)

10 ft (3,1 m)

Maximum Coverage Area 

(CPVC Pipe)

100 ft² (9,3 m²)

Deflector Position (CPVC Pipe)

1-1/2 in. to 4 in. (40 to 100 mm) below 

upper deck for wood truss construction 

or bar joist construction (Ref. Figure 2).
1-1/2 in. to 2 in, (40 to 50 mm) below 

solid wood or composite wood joists 

(Ref. Figure 3).

Minimum Distance Away from 

Trusses (CPVC Pipe)

4-1/2 in. (114 mm)

Remote Area (CPVC Pipe)

The remote area is 1000 ft² (93 m²)
The remote area does not include any 

additional sprinklers required for pro-

tection of BLAZEMASTER CPVC that 

is offset over an obstruction.

Required Density (CPVC Pipe)

0.10 gpm/ft² (4,1 mm/min)

Minimum Operating Pressure 

(CPVC Pipe)

10 psi (0,7 bar)

Obstructions (CPVC Pipe)

All obstruction criteria per NFPA for 

standard spray sprinklers apply (Ref. 

Figure 8), unless modified by this tech-

nical data sheet.

UL Listed Use of BLAZEMASTER 

CPVC Piping with Model CC1 

Sprinklers

BLAZEMASTER CPVC product may 

be used in concealed spaces requir-

ing automatic sprinklers, when used in 

conjunction with Model CC1 Sprinklers. 

In order to use the BLAZEMASTER 

CPVC product for wood truss or bar 

joist construction, the horizontal run of 

pipe must be a maximum of 6 in. (150 

mm) above the ceiling or non-combus-

tible ceiling insulation, or 1/3 the depth 

of concealed space (as measured from 

the top surface of the ceiling to the 

bottom of the deck above), whichever 

is smaller (Ref. Figure 2). For insulation 

filled solid wood or composite wood 

joist construction, the horizontal run of 

pipe must be a maximum of 6 in. (150 

mm) above ceiling or non-combusti-

ble ceiling insulation, or 1/3 the depth 

of concealed space (as measured 

from the top surface of the ceiling to 

the bottom surface of the joist insula-

tion above), whichever is smaller (Ref. 

Figure 3). The CPVC piping can then 

be used to supply the Model CC1 

Sprinklers, as well as the sprinklers 

below the ceiling. Unless modified by 

this Technical Data Sheet, all other 

guidelines of the “BLAZEMASTER — 

Installation Instructions & Technical 

Manual” must be met. When using 1 

in. (DN25) or larger pipe, a hanger must 

be located at the truss nearest a sprig 

for purposes of restraint. If using 3/4 

in. (DN19) piping, all sprigs over 12 

in. (305 mm) must be laterally braced 

using methods described in the NFPA 

standards.
Where the CPVC must be offset up 

and over an obstruction and the pipe 

exceeds the allowed horizontal posi-

tioning requirements specified above 

as well as shown in Figure 2 and 3, 

additional Model CC1 Sprinklers are to 

be installed as shown in Figure 2 and 

3 to protect the BLAZEMASTER CPVC 

product.
A minimum lateral distance of 18 in. 

(460 mm) must be maintained between 

the CPVC pipe and heat pumps, fan 

motors, and heat lamps.

-

-

-
-

-

-

1

6

3

5

4

2

WRENCH

FLATS

7/16" (11,1 mm)

NOMINAL MAKE-IN

SPRINKLER

FRAME

ARMS

2-1/4"

(57,2 mm)

1/2" NPT

THREAD

RELIEF

Frame

Button

Deflector

Bulb

2

1

3

4

Components:

5

6

1-1/16"

(27,0 mm)

Sealing

Assembly

Compression

Screw

FIGURE 1 

MODEL CC1 SPRINKLER

Содержание tyco CC1

Страница 1: ...this product Concealed spaces between floors as well as low pitch attics are inherently shallow Standard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challeng...

Страница 2: ...R CPVC that is offset over an obstruction Required Density CPVC Pipe 0 10 gpm ft 4 1 mm min Minimum Operating Pressure CPVC Pipe 10 psi 0 7 bar Obstructions CPVC Pipe All obstruction criteria per NFPA...

Страница 3: ...SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE PIPE RUN OBSTRUCTION CEILING MODEL CC1 SPRINKLER UPPER DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 2 51 mm MAXIMUM 6...

Страница 4: ...ay be constructed of 1 4 in 6 4 mm plywood to prevent heat from escaping beyond the area For non combustible insulation filled solid wood joist or composite wood joist construction Ref Figure 6 the re...

Страница 5: ...ITH PIPE RUN CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6...

Страница 6: ...15 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH TRUSSES NOT NECESSARILY WITH PIPE RUN UPPER DECK MODEL CC1 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER...

Страница 7: ...the W Type 20 End B Sprinkler Wrench Ref Figure 9 for installation of the Model CC1 Sprinklers by applying the wrench to the sprinkler wrench flats only 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7...

Страница 8: ...cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers dama...

Отзывы: