TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
11
Configuring the Thermostat Controller
The thermostat controller ships from the factory with
default settings for all configurable parameters. The
default settings are shown in Table 6. To reconfigure
the parameters, follow the steps in this section.
1.
To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note:
If the
Password
parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed.
Use the
UP/DOWN
arrow keys to indicate the
configured password, then press the
MODE
key to
proceed through the Installer Configuration Menu
parameters.
2.
Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 6.
3.
When the desired parameter is displayed, use the
UP/DOWN
arrow keys to choose the desired
selection option.
4.
Press and release the center key to continue
scrolling through the parameters.
St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FI
G
:r
m
_t
m
p
Figure 13: Increasing Room Temperature Setpoints
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hours
Unoccupied Time
= 6 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Stand-By
= 2 Hrs
Unoccupied Time
= 6 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Time
Unoccupied Time Elapsed
= Unoccupied Mode
FI
G
:u
noc
c6s
b
2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 14: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hrs
Unoccupied Time
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Time
FI
G
:unoc
c0
sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 15: Unoccupied Timer Set to 0 Hours and Stand-by Timer Set to 2 Hours