TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification 
Capability, Fan Control, and Occupancy Sensing Capability 

20

DehuCool

1

Sets the maximum dehumidification 
cooling output (TEC2036[H]-2, and 
TEC2056[H]-2 models). This 
parameter can be used only if the 
dehumidification sequence is 
enabled.
Default: 

100%

Range: 

20.0

 to 

100.0%

Note:

This parameter can be used to balance smaller reheat loads 

installed with regard to the capacity of the cooling coil.

St-By TM

Sets stand-by timer value when 
used with occupancy sensor; time 
delay between moment where 
occupancy sensor detected the last 
movement in the area and the time 
which the thermostat stand-by mode 
and setpoints become active.
Default: 

0.5 hours

Range: 

0.5

 to 

24.0

 

hours

, in 0.5 hour increments

Unocc TM

Sets Unoccupied Timer Value when 
used with occupancy sensor; time 
delay between the moment where 
the thermostat toggles to stand-by 
mode and the time which the 
thermostat unoccupied mode and 
setpoints become active.
Default: 

0.0

 hours

0.0 hours 

or Factory Value: Setting this parameter to its default 0 

value disables the occupied timer and prevents the thermostat from 
drifting from stand-by mode to unoccupied mode when occupancy 
sensor functions are used.
Range: 

0.0 

to 

24.0

 

hours

 in 0.5 hour increments.

St-By HT

Sets Stand-by heating setpoint 
when used with occupancy sensor; 
value is between occupied and 
unoccupied heating setpoints.
Default:

 69.0°F/20.6°C

Range: 

40.0°F/4.5°C

 to 

90.0°F/32.0°C

Note:

When adjusting the 

temperature, press the 

UP/

DOWN

 arrow keys to 

change the temperature in 
0.5F°/0.5C° increments; 
press and hold the 

UP/DOWN

 arrow keys 

to change the temperature 
in 5.0F°/5.0C° increments.

St-By CL

Sets Stand-by cooling setpoint limit 
when used with occupancy sensor; 
value is between occupied and 
unoccupied cooling setpoints.
Default: 

78.0°F/25.6°C

Range: 

54.0°F/12.0°C

 to 

100.0°F/37.5°C

Unocc HT

Sets the Unoccupied Heating 
setpoint value.
Default: 

62.0°F/16.5°C

Range: 

40.0°F/4.5°C

 to 

90.0°F/32.0°C

Unocc CL

Sets the Unoccupied Cooling 
setpoint value.
Default: 

80.0°F/26.5°C

Range: 

54.0°F/12.0°C

 to

100.0°F/37.5°C

Heat max

Sets the Occupied and Unoccupied 
maximum Heating setpoint values.
Default: 

90.0°F/32.0°C

Range: 

40.0°F/4.5°C

 to

90.0°F/32.0°C

Cool min

Sets the Occupied and Unoccupied 
minimum Cooling setpoint values.
Default: 

54.0°F/12.0°C

Range: 

54.0°F/12.0°C

 to

100.0°F/37.5°C

Table 6:  Installer Configuration Menu

 

 (Part 5 of 8)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC20x6-4 Series

Страница 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Страница 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Страница 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Страница 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Страница 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Страница 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Страница 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Страница 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Страница 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Страница 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Страница 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Страница 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Страница 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Страница 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Страница 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Страница 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Страница 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Страница 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Страница 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Страница 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Страница 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Страница 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Страница 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Страница 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Страница 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Отзывы: