TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
20
DehuCool
1
Sets the maximum dehumidification
cooling output (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default:
100%
Range:
20.0
to
100.0%
Note:
This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
St-By TM
Sets stand-by timer value when
used with occupancy sensor; time
delay between moment where
occupancy sensor detected the last
movement in the area and the time
which the thermostat stand-by mode
and setpoints become active.
Default:
0.5 hours
Range:
0.5
to
24.0
hours
, in 0.5 hour increments
Unocc TM
Sets Unoccupied Timer Value when
used with occupancy sensor; time
delay between the moment where
the thermostat toggles to stand-by
mode and the time which the
thermostat unoccupied mode and
setpoints become active.
Default:
0.0
hours
0.0 hours
or Factory Value: Setting this parameter to its default 0
value disables the occupied timer and prevents the thermostat from
drifting from stand-by mode to unoccupied mode when occupancy
sensor functions are used.
Range:
0.0
to
24.0
hours
in 0.5 hour increments.
St-By HT
Sets Stand-by heating setpoint
when used with occupancy sensor;
value is between occupied and
unoccupied heating setpoints.
Default:
69.0°F/20.6°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Note:
When adjusting the
temperature, press the
UP/
DOWN
arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN
arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
St-By CL
Sets Stand-by cooling setpoint limit
when used with occupancy sensor;
value is between occupied and
unoccupied cooling setpoints.
Default:
78.0°F/25.6°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Unocc HT
Sets the Unoccupied Heating
setpoint value.
Default:
62.0°F/16.5°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Unocc CL
Sets the Unoccupied Cooling
setpoint value.
Default:
80.0°F/26.5°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Heat max
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Cool min
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.0°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Table 6: Installer Configuration Menu
(Part 5 of 8)
Parameter
Appearing
on Display
Description and Default
Selection Options