TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
12
Note:
Pressing the
FAN
key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 6.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition displays locally when the
input closes. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat controller.
Each input can be configured to the Selection Options
included in Table 6.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequence
of operation selected. For two-pipe applications using a
changeover sensor, choose the selection option
(0): Cooling Only
. Changeover occurs between
Cooling Only
and
Heating Only
. See Figure 16
through Figure 21 for sequence of operation examples.
Table 4: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
Control
Curve
Terminal Numbers Used (See Table 2 and Figure 5.)
On/Off Control
Floating Control
Proportional
0 to 10 VDC Control
(0): Cooling Only
See Figure 16.
10:
Normally Open
(N.O.) Cooling
11:
Normally Closed
(N.C.) Cooling
10:
Open Cooling
11:
Closed Cooling
10:
Proportional Cooling
(1): Heating Only
See Figure 17.
10:
N.O. Heating
11:
N.C. Heating
10:
Open Heating
11:
Closed Heating
10:
Proportional Heating
(2): Cooling with Reheat
See Figure 18.
6 and 7:
Reheat
10:
N.O. Cooling
11:
N.C. Cooling
6 and 7:
Reheat
10:
Open Cooling
11:
Closed Cooling
6 and 7:
Reheat
10:
Proportional Cooling
(3): Heating with Reheat
See Figure 19.
6 and 7:
Reheat
10:
N.O. Heating
11:
N.C. Heating
6 and 7:
Reheat
10:
Open Heating
11:
Closed Heating
6 and 7:
Reheat
10:
Proportional Heating