TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification 
Capability, Fan Control, and Occupancy Sensing Capability 

6

Table 2:  TEC20x6(H)-4 and TEC20x6H-4+PIR Series Thermostat Controller Terminals 

Terminal 
Number

Terminal Label by Model

Function

TEC2016-4, 
TEC2016H-4, 
TEC2016H-4+PIR 
(On/Off Control)

TEC2026-4, 
TEC2026H-4, 
TEC2026H-4+PIR 
TEC2036-4, 
TEC2036H-4, 
TEC2036H-4+PIR 
(On/Off or Floating 
Control)

TEC2046-4, 
TEC2046H-4, 
TEC2046H-4+PIR, 
TEC2056-4, 
TEC2056H-4, 
TEC2056H-4+PIR 
(Proportional 
0 to 10 VDC Control)

1

Fan-H

Fan-H

Fan-H

Fan On – High

2

Fan-M

Fan-M

Fan-M

Fan On – Medium

3

Fan-L

Fan-L

Fan-L

Fan On – Low

4

24 V~ Hot

24 V~ Hot

24 V~ Hot

24 VAC from Transformer

5

24 V~ Com

24 V~ Com

24 V~ Com

24 VAC from Transformer 
(Common)

6

BO5 Aux

BO5 Aux

BO5 Aux

Auxiliary Binary Output

7

BO5 Aux

BO5 Aux

BO5 Aux

Auxiliary Binary Output

8

BO3

BO3

Blank

Open Heat

9

Blank

BO4

AO2

Close Heat

10

Blank

BO1

AO1

Open Cool

11

BO2

BO2

Blank

Close Cool

12

BI1

BI1

BI1

Configurable Binary Input 1

13

RS

RS

RS

Remote Sensor

14

Scom

Scom

Scom

Sensor Common

15

BI2

BI2

BI2

Configurable Binary Input 2

16

UI3

UI3

UI3

Configurable Universal Input 3

Figure 7: TEC20x6(H)-4 and TEC20x6H-4+PIR Series Thermostat Controller with 

Same Power Source for Auxiliary Contact

F

IG

:TEC2

0x6

H

4_S

A

M

BI2

UI3

BI1

Scom

- OR -

Remote Inputs

Supply Sensor
Changeover Sensor

Voltage-Free
Contact
• COC/NH
  Normally Heat
  Closed Contact
  = Cold Water
• COC/NC
  Normally Cool
  Closed Contact
  = Hot Water

Voltage-Free
Contact
• Door
• Remote
  Override
• Filter Alarm
• Service Alarm

Voltage-Free
Contact
• Remote NSB
• Motion
• Window

Same 24 VAC

Power Source for Auxiliary Output

(24 VAC Maximum)

Power and Fan

BO5

Aux

BO5

Aux

Aux Contact
(Isolated Common)
• Reheat
• Lighting
• On/Off Actuation
• Exhaust Fan

Aux

24 VAC

Thermostat Power

24 V~

Com

24 V~

Hot

Fan
 -H

Fan
 -M

Fan
 -L

Содержание TEC20x6-4 Series

Страница 1: ...less Thermostat Controllers are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or p...

Страница 2: ...Metasys System Location Guide LIT 12011294 Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Страница 3: ...u have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the m...

Страница 4: ...ire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB Note I...

Страница 5: ...EC20x6H 4 PIR Series Thermostat Controller Terminals Figure 6 TEC20x6 H 4 and TEC20x6H 4 PIR Series Thermostat Controller with Separate Power Source for Auxiliary Contact FIG TEC20x6H4_SEP BI2 UI3 BI1...

Страница 6: ...Aux BO5 Aux BO5 Aux Auxiliary Binary Output 8 BO3 BO3 Blank Open Heat 9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 R...

Страница 7: ...ting Valve 24 V Hot BO3 N C Cooling Valve FIG TEC2016H4_onoff Figure 9 Wiring TEC2026 H 4 TEC2026H 4 PIR TEC2036 H 4 and TEC2036H 4 PIR Thermostat Controllers for On Off Control Two Pipe Applications...

Страница 8: ...key also allows access to the Installer Configuration Menu See the Configuring the Thermostat Controller section C F key hospitality models changes the temperature scale to either Celsius or Fahrenhe...

Страница 9: ...te For models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current...

Страница 10: ...tic LEDs The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup The LEDs do not light up or brighten after the initial 30 minute period Se...

Страница 11: ...he UP DOWN arrow keys to choose the desired selection option 4 Press and release the center key to continue scrolling through the parameters St By Heat 69 F Occ Heat 72 F Occ Cool 75 F St By Cool 78 F...

Страница 12: ...ration SeqOpera Choose the appropriate sequence of operation The modes presented are user dependent on the sequence of operation selected For two pipe applications using a changeover sensor choose the...

Страница 13: ...Cooling with Reheat See Figure 18 6 and 7 Reheat 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 10 Open Cooling 11 Closed Cooling 6 and 7 Reheat 10 Proportional Cooling 3 Heating with Reheat See Figure...

Страница 14: ...Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling...

Страница 15: ...tting Figure 22 This operation applies to the occupied mode when the fan is set to Auto Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Se...

Страница 16: ...e fan to low speed the chilled water valve opens to the specified maximum value set by CoolMax the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint as sens...

Страница 17: ...ted if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan mode A window alarm appears indicating that the window needs to be closed to resume heating or cooling These settings dis...

Страница 18: ...mperature is available as a point for integration and UI3 Status is not available as a point for integration MenuScro Gives the option of having the display continuously scroll the parameters Default...

Страница 19: ...Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a changeover sensor to allow changeo...

Страница 20: ...from drifting from stand by mode to unoccupied mode when occupancy sensor functions are used Range 0 0 to 24 0 hours in 0 5 hour increments St By HT Sets Stand by heating setpoint when used with occu...

Страница 21: ...int Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use Both the heating and cooling setpoints are changed simult...

Страница 22: ...use this selection option 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxiliary functions via a separate and dedi...

Страница 23: ...e acting 0 to 100 10 to 0 VDC DA Direct acting 0 to 100 0 to 10 VDC Reheat Sets the duty cycle time for reheat output if Option 2 3 or 5 is chosen in the SeqOpera parameter Default 0 1 10 seconds six...

Страница 24: ...y sensing capability 5 TEC 6H PIR Accessory Cover can be used to replace the existing cover on a non PIR TEC20x6H 4 Series Thermostat Controller to provide occupancy sensing capability TEC20x6 H 4 and...

Страница 25: ...le E27734 CCN XAPX Under UL 873 Temperature Indicating and Regulating Equipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Transmitter FCC Identification pending Ca...

Отзывы: