TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
19
Pipe No
Selectable number of pipes in the
system.
Default:
4.0 Pipes
(2.0 Pipes):
Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes):
Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
CntrlTyp
Defines the control output for the
type of valves used in the
installation (TEC2026-2,
TEC2026H-2, TEC2036-2, and
TEC2036H-2 models).
Default:
Floating
(On/Off):
For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating):
For proportional three-wire control of 24 VAC floating
valves.
SeqOpera
Determines the sequence of
operation.
Default:
1
(0):
Cooling Only (Off-Cool). The default is
Cool
.
(1):
Heating Only (Off-Heat). The default is
Heat
.
(2):
Cooling and Reheat (Off-Auto*-Heat-Cool). The default is
Auto
.
(3):
Heating and Reheat (Off-Heat). The default is
Heat
.
(4):
Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is
Auto
.
(5):
Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is
Heat
.
* Auto can be disabled with the
AutoMode
parameter. When Auto
is disabled, the default for
(2)
and
(4)
is
Heat
.
Note:
Choose the selection option
(0): Cooling Only
when using a
changeover sensor to allow changeover to occur between
Cooling
Only
and
Heating Only
. Choose the selection option
(2): Cooling
and Reheat
when using a changeover sensor to allow changeover
to occur between
Cooling and Reheat
and
Heating and Reheat
.
Fan Menu
Sets the Fan Mode options.
Default:
4
(0):
Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is
High
.
(1):
Low-High: Two-speed configuration using two fan relays (L-H).
The default is
High
.
(2):
Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is
High
.
(3):
Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is
High
.
(4):
On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is
Auto
.
DHumiLCK
Locks out the dehumidification
capability (TEC2036[H]-2, and
TEC2056[H]-2 models).
Default:
on
(off):
Dehumidification is locked out.
(on):
Dehumidification is allowed.
%RH set
1
Sets the dehumidification setpoints
(TEC2036[H]-2, and TEC2056[H]-2
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default:
50.0% RH
Range:
30.0
to
95.0% RH
DehuHyst
1
Sets the dehumidification hysteresis
(deadband) (TEC2036[H]-2, and
TEC2056[H]-2 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default:
5.0% RH
Range:
2.0
to
20.0% RH
Table 6: Installer Configuration Menu
(Part 4 of 8)
Parameter
Appearing
on Display
Description and Default
Selection Options