TEC20x6(H)-4 and TEC20x6H-4+PIR Series Wireless Thermostat Controllers with Dehumidification
Capability, Fan Control, and Occupancy Sensing Capability
22
Cal RS
Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Cal RH
Sets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(TEC2036-4, TEC2036H-4,
TEC2036H-4+PIR, TEC2056-4,
TEC2056H-4, and
TEC2056H-4+PIR models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default:
0.0% RH
Range:
-15.0% RH
to
15.0% RH
(adjustable in 1% RH increments)
Aux cont
Determines the auxiliary contact
function and configuration.
Default:
0
(0)
Not used,
or used for
reheat
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
(1)
Auxiliary
N.O.
Occupied
= contact
closed
Unoccupied
= contact
open
The output
aligns with
occupancy.
(2)
Auxiliary
N.C.
Occupied
= contact open
Unoccupied
= contact
closed
(3*)
Do not use this selection option.
(4*)
Do not use this selection option.
(5)
Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network
variable.
The output
aligns with
the
secondary
network
occupancy
command.
* If option
(3)
or
(4)
is used, it functions like option
(1)
or
(2)
,
respectively.
Auto Fan
Affects the auto mode of operation
for the following
Fan Menu
parameter selection options only:
•
(2):
Low-Med-High-Auto
•
(3):
Low-High-Auto
Default:
AS
(AS AD):
The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only
re-activated when there is a heating or cooling demand.
(AS):
The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
FL time
Sets the maximum actuator stroke
timing (floating
CntrlTyp
TEC2026-4, TEC2026H-4,
TEC2026H-4+PIR, TEC2036-4,
TEC2036H-4, and
TEC2036H-4+PIR models).
Default:
1.5 min
Range:
0.5
to
9.0 min
(adjustable in 0.5 minute increments)
Table 6: Installer Configuration Menu
(Part 7 of 8)
Parameter
Appearing
on Display
Description and Default
Selection Options