TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions 

5

Setup and Adjustments

Overview

Figure 7

 

shows the front cover of the thermostat 

controller, including features used for setting up and 
adjusting the thermostat controller. 

User Interface Keys

The user interface consists of keys on the front cover 
as illustrated in Figure 7. The function of each key is as 
follows:

Use  the 

YES/SCROLL

 key to:

-

confirm menu selections and to advance to the 
next menu item

-

stop the Status Display Menu from scrolling 
and to manually scroll to the next parameter on 
the menu

Note:

When the thermostat controller is left 

unattended for 45 seconds, the display resumes 
scrolling.

Use  the 

NO

 key to decline a parameter change and 

to advance to the next menu item.

Use  the 

MENU

 key to:

-

access the Main User Menu or to exit the menu 
(See the 

Main User Menu

 section.)

-

access the Installer Configuration Menu or to 
exit the menu (See the 

Installer Configuration 

Menu 

section.)

UP/DOWN

 arrow keys change the configuration 

parameters and activate a setpoint adjustment.

Light-Emitting Diodes (LEDs)

System Activity LEDs indicate the status and actions of 
the thermostat controller.

The 

FAN

 LED is on when the fan is on.

The 

HEAT

 LED is on when heating or reheat is on.

The 

COOL

 LED is on when cooling is on.

The Status LED, located beneath the cover, flashes at 
five-second intervals to provide indication of the 
network status of the thermostat controller. See 
Table 3.

Backlit Liquid Crystal Display (LCD)

The thermostat controller includes a 2-line, 8-character 
backlit display. Low-level backlighting is present during 
normal operation, and it brightens when any user 
interface key is pressed. The backlight returns to low 
level when the thermostat controller is left unattended 
for 45 seconds.

Status Display Menu

 

The Status Display Menu displays during normal 
operation. This menu scrolls through several 
parameters:

Room Temperature

System Mode

Schedule Status (Occupied/Unoccupied/Override)

Outdoor Temperature – An outdoor air temperature 
sensor must be connected.

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Figure 7: Front Cover

F

IG

:T

E

C

2

0

0

x

-3

_

fr

n

t

YES

NO

70.0ºF

Room Temp

Backlit

Plain-Text

LCD

System

Activity

LEDs

Intuitive

Operation

Keys

Status LED 

(beneath cover)

Table 3:  Status LED

Flashes per 
5-Second 
Interval

Condition Indicated

1

Power On

2

Power On, Communicating

3

Power On, Communicating, Found 
Wireless Network

4

Power On, Communicating, Found 
Wireless Network, Communicating with 
TEC20 Coordinator

Содержание TEC2003-3

Страница 1: ... equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the thermostat controller This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part...

Страница 2: ...ion Guide LIT 12011294 Mounting the Thermostat Controller Follow these steps to mount the thermostat controller 1 Use a Phillips head screwdriver to loosen the security screw on the bottom of the cover 2 Pull the bottom edge of the cover and open the thermostat controller as illustrated in Figure 1 3 Carefully pull the locking tabs on the right side of the mounting base and unlock the Printed Circ...

Страница 3: ...rmostat controller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 and Table 2 Note If multiple wires are inserted into the screw terminals be sure to properly twist the wires together prior to inserting them into the screw terminals 2 Carefully push any excess wire back into the wall Seal the hole in the wall with fireproof ma...

Страница 4: ...ensor Auxiliary Outdoor Air Sensor Cool 2 G Fan Scom RS MS OS Isolated Contact Lighting On Off Actuation Exhaust Fan Remote Room Sensor Table 2 TEC2003 3 Thermostat Controller Terminals Terminal Number Terminal Label Function 1 Y2 Energizes on a call for Second Stage Cooling 2 Y1 Energizes on a call for First Stage Cooling 3 G Energizes Fan in accordance with Selected Fan Mode 4 RC 24 VAC from Equ...

Страница 5: ...controller The FAN LED is on when the fan is on The HEAT LED is on when heating or reheat is on The COOL LED is on when cooling is on The Status LED located beneath the cover flashes at five second intervals to provide indication of the network status of the thermostat controller See Table 3 Backlit Liquid Crystal Display LCD The thermostat controller includes a 2 line 8 character backlit display ...

Страница 6: ...s Mesh Network Settings Use the following process to configure the wireless mesh network settings 1 Select a PAN ID and Channel Use these same values for every TEC Wireless Thermostat Controller and the associated coordinator on the same wireless mesh network 2 Select a Com Address for each TEC Wireless Thermostat Controller 1 to 254 This address must be unique to each TEC Wireless Thermostat Cont...

Страница 7: ...rol card which provides an alarm should there be a malfunction Filter A Filter alarm is displayed This alarm can be connected to a differential pressure switch that monitors a filter RemOVR Temporary occupancy request via a remote input This override function is controlled by a manual remote occupancy override When enabled this condition disables the override capability of the thermostat controlle...

Страница 8: ...efault 1 0C 2 0F Range 1 0C 2 0F to 2 0C 4 0F adjustable in 0 5C 1 0F increments Fan cont Determines how the fan is activated in response to a call for heating or cooling Default on off Enables the thermostat controller to activate the fan in response to a call for cooling only on Enables the thermostat controller to activate the fan in response to a call for heating or cooling When there is a cal...

Страница 9: ...g stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second cooling stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages H lock Discontinues heating operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed and...

Страница 10: ... Menu of the thermostat controller when in the occupied state is to set the permanent temperature setpoint Permanent setpoints are stored in the programmed schedule To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied Modes follow the steps in Table 5 When changing the temperatures press the keys once to change the temperature in 0 5F 0 5C increments press and hold ...

Страница 11: ...e 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu Selecting the Fan Mode The thermostat controller has three fan mode settings On Fan Mode on Energizes the fan all the time for both occupied and unoccupied stat...

Страница 12: ...ermostat controller contact the nearest Johnson Controls representative Table 6 Display Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input BI2 Filter Indicates that the filter s is dirty in accordance with the programmable Binary Input BI2 Table 7 Accessories Order Separately Product Code Number Description ACC INSL 0 Foam Ins...

Страница 13: ...90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0 F to 100 0 F 38 0 C in 0 5 Increments Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient NTC Thermistor Resolution 0 1C 0 2F Control Accuracy 0 5C 0 9F at 21 0 C 70 0 F Typical Calibrated Auxiliary Outdoor Air Temperature Indication Range 40 0 C 40 0 F to 50 0 C 122 0 F Minimum Deadband 1C 2F between Heating and Cooling Ambie...

Отзывы: