TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions
9
Programming the Thermostat Controller
After configuring the thermostat controller by means of
the Installer Configuration Menu, program its operating
parameters by means of the Main User Menu. Access
this menu by pressing the
MENU
key during normal
operation. The Main User Menu contains the basic
operating features of the thermostat controller.
The Main User Menu also uses Auto Help, which is
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,
continue with the programming selection. When the
thermostat controller is in the Main User Menu and is
left unattended for 45 seconds, the menu reverts to the
Status Display Menu.
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0C°/0.0C°F
Range:
-2.5C°/-5.0F°
to
2.5C°/5.0F°
adjustable in 0.5C°/1.0F°
increments
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0C°/0.0F°
Range:
-2.5C°/-5.0F°
to
2.5C°/5.0F°
adjustable in 0.5C°/1.0F°
increments
H stage
Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second heating stage is
not needed.
Default:
2.0
(1.0):
One Stage
(2.0):
Two Stages
C stage
Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second cooling stage is
not needed.
Default:
2.0
(1.0):
One Stage
(2.0):
Two Stages
H lock
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default:
49°C/120°F
Range:
-26°C/
-15°F
to
49°C/120°F
adjustable in 5C°/5F°
increments
C lock
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default:
-40°C/-40°F
Range:
-40°C/-40°F
to
35°C/95°F
adjustable in
5C°/5F°
increments
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default:
n.o.
(n.c.):
Contact open = Occupied; contact closed = Unoccupied.
(n.o.):
Contact closed = Occupied; contact open = Unoccupied.
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
1.
When adjusting the numeric value, press the
UP
or
DOWN
arrow key to change the value by single increments; press and
hold the
UP
or
DOWN
arrow key to change the numeric value in increments of ten.
2.
When adjusting the temperature, press the
UP
or
DOWN
arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the
UP
or
DOWN
arrow key to change the value in 5.0F°/5.0C° increments.
Table 4: Installer Configuration Menu (Part 4 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options