TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions

8

Frost pr

Provides a minimum heating 
setpoint of 5.5°C/42.0°F to prevent 
freezing in the zone controlled by 
the thermostat controller.
Default: 

off

(on):

 Enabled

(off):

 Disabled

Heat max

2

Sets the Occupied and Unoccupied 
maximum Heating setpoint values.
Default: 

32.0°C/90.0°F

Range: 

4.5°C/40.0°F/

to 

32.0°C/90.0°F

Cool min

2

Sets the Occupied and Unoccupied 
minimum Cooling setpoint values.
Default: 

12.0°C/54.0°F

Range: 

12.0°C/54.0°F

 to 

37.5°C/100.0°F

Anticycl

Anti-Short Cycle timer sets the 
minimum on/off times for heating 
and cooling stages.
Default: 

2.0 min

Range: 

0.0

 to 

5.0 min

 adjustable in 1-minute increments

Set the anti-short cycle timer to 

0.0 min

 for equipment that already 

has its own anti-short cycle timer.

Heat cph

Sets the maximum number of 
Heating cycles per hour.
Default: 

4.0

Range: 

3.0

 to 

8.0

 cycles per hour

Cool cph

Sets the maximum number of 
Cooling cycles per hour.
Default: 

4.0

Range: 

3.0

 or 

4.0

 cycles per hour

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

1.0C°/2.0F°

Range: 

1.0C°/2.0F°

 to 

2.0C°/4.0F°

 adjustable in 

0.5C°/1.0F°

 

increments

Fan cont

Determines how the fan is activated 
in response to a call for heating or 
cooling.
Default: 

on

(off):

 Enables the thermostat controller to activate the fan in 

response to a call for cooling only.

(on):

 Enables the thermostat controller to activate the fan in 

response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the 
equipment fan and limit control.

Fan del

Fan delay extends fan operation 
after a heating or cooling cycle has 
ended.
Default 

off

(on):

 Extends fan operation by 60 seconds after a heating or cooling 

cycle has ended.

(off):

 No extension of fan operation after a heating or cooling cycle 

has ended.
The fan delay is only active when the fan is in the Auto mode.

TOccTime

Sets the duration of the Temporary 
Occupancy Time when the heating 
or cooling setpoints in the Occupied 
mode are established by:
• 

an Override Function enabled in 
the Main User Menu (when the 
thermostat controller is in the 
Unoccupied mode)

• 

a temporary heating or cooling 
setpoint

default: 

3.0 hrs

Range: 

0.0

 to 

12.0 hrs

 adjustable in 1-hour increments

Table 4:  Installer Configuration Menu  (Part 3 of 4)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2003-3

Страница 1: ... equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the thermostat controller This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part...

Страница 2: ...ion Guide LIT 12011294 Mounting the Thermostat Controller Follow these steps to mount the thermostat controller 1 Use a Phillips head screwdriver to loosen the security screw on the bottom of the cover 2 Pull the bottom edge of the cover and open the thermostat controller as illustrated in Figure 1 3 Carefully pull the locking tabs on the right side of the mounting base and unlock the Printed Circ...

Страница 3: ...rmostat controller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 and Table 2 Note If multiple wires are inserted into the screw terminals be sure to properly twist the wires together prior to inserting them into the screw terminals 2 Carefully push any excess wire back into the wall Seal the hole in the wall with fireproof ma...

Страница 4: ...ensor Auxiliary Outdoor Air Sensor Cool 2 G Fan Scom RS MS OS Isolated Contact Lighting On Off Actuation Exhaust Fan Remote Room Sensor Table 2 TEC2003 3 Thermostat Controller Terminals Terminal Number Terminal Label Function 1 Y2 Energizes on a call for Second Stage Cooling 2 Y1 Energizes on a call for First Stage Cooling 3 G Energizes Fan in accordance with Selected Fan Mode 4 RC 24 VAC from Equ...

Страница 5: ...controller The FAN LED is on when the fan is on The HEAT LED is on when heating or reheat is on The COOL LED is on when cooling is on The Status LED located beneath the cover flashes at five second intervals to provide indication of the network status of the thermostat controller See Table 3 Backlit Liquid Crystal Display LCD The thermostat controller includes a 2 line 8 character backlit display ...

Страница 6: ...s Mesh Network Settings Use the following process to configure the wireless mesh network settings 1 Select a PAN ID and Channel Use these same values for every TEC Wireless Thermostat Controller and the associated coordinator on the same wireless mesh network 2 Select a Com Address for each TEC Wireless Thermostat Controller 1 to 254 This address must be unique to each TEC Wireless Thermostat Cont...

Страница 7: ...rol card which provides an alarm should there be a malfunction Filter A Filter alarm is displayed This alarm can be connected to a differential pressure switch that monitors a filter RemOVR Temporary occupancy request via a remote input This override function is controlled by a manual remote occupancy override When enabled this condition disables the override capability of the thermostat controlle...

Страница 8: ...efault 1 0C 2 0F Range 1 0C 2 0F to 2 0C 4 0F adjustable in 0 5C 1 0F increments Fan cont Determines how the fan is activated in response to a call for heating or cooling Default on off Enables the thermostat controller to activate the fan in response to a call for cooling only on Enables the thermostat controller to activate the fan in response to a call for heating or cooling When there is a cal...

Страница 9: ...g stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation of a two stage thermostat controller to a single stage thermostat controller when the second cooling stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages H lock Discontinues heating operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed and...

Страница 10: ... Menu of the thermostat controller when in the occupied state is to set the permanent temperature setpoint Permanent setpoints are stored in the programmed schedule To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied Modes follow the steps in Table 5 When changing the temperatures press the keys once to change the temperature in 0 5F 0 5C increments press and hold ...

Страница 11: ...e 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu Selecting the Fan Mode The thermostat controller has three fan mode settings On Fan Mode on Energizes the fan all the time for both occupied and unoccupied stat...

Страница 12: ...ermostat controller contact the nearest Johnson Controls representative Table 6 Display Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input BI2 Filter Indicates that the filter s is dirty in accordance with the programmable Binary Input BI2 Table 7 Accessories Order Separately Product Code Number Description ACC INSL 0 Foam Ins...

Страница 13: ...90 0 F in 0 5 Increments Cooling Control 12 0 C 54 0 F to 100 0 F 38 0 C in 0 5 Increments Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient NTC Thermistor Resolution 0 1C 0 2F Control Accuracy 0 5C 0 9F at 21 0 C 70 0 F Typical Calibrated Auxiliary Outdoor Air Temperature Indication Range 40 0 C 40 0 F to 50 0 C 122 0 F Minimum Deadband 1C 2F between Heating and Cooling Ambie...

Отзывы: