TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions
8
Frost pr
Provides a minimum heating
setpoint of 5.5°C/42.0°F to prevent
freezing in the zone controlled by
the thermostat controller.
Default:
off
(on):
Enabled
(off):
Disabled
Heat max
2
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
32.0°C/90.0°F
Range:
4.5°C/40.0°F/
to
32.0°C/90.0°F
Cool min
2
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
12.0°C/54.0°F
Range:
12.0°C/54.0°F
to
37.5°C/100.0°F
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default:
2.0 min
Range:
0.0
to
5.0 min
adjustable in 1-minute increments
Set the anti-short cycle timer to
0.0 min
for equipment that already
has its own anti-short cycle timer.
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default:
4.0
Range:
3.0
or
4.0
cycles per hour
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
1.0C°/2.0F°
Range:
1.0C°/2.0F°
to
2.0C°/4.0F°
adjustable in
0.5C°/1.0F°
increments
Fan cont
Determines how the fan is activated
in response to a call for heating or
cooling.
Default:
on
(off):
Enables the thermostat controller to activate the fan in
response to a call for cooling only.
(on):
Enables the thermostat controller to activate the fan in
response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the
equipment fan and limit control.
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default
off
(on):
Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off):
No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
•
an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
•
a temporary heating or cooling
setpoint
default:
3.0 hrs
Range:
0.0
to
12.0 hrs
adjustable in 1-hour increments
Table 4: Installer Configuration Menu (Part 3 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options