T600HCx-3 Single-Stage Thermostats Installation Instructions
6
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default:
0
Function
Lockout Level
(0)
(1)
(2)
Occupancy
Override
Access
Access
No Access
Permanent
Temperature
Setpoints
Access
No Access
No Access
Temporary
Temperature
Setpoints
Access
Access
No Access
System Mode
Setting
Access
No Access
No Access
Fan Mode Setting
Access
No Access
No Access
Schedules
Setting
2
Access
No Access
No Access
Clock Setting
2
Access
Access
Access
Permanent Hold
2
Access
No Access
No Access
Pwr del
3
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default:
10.0 sec
Range:
10.0
to
120.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default:
off
(on):
Enabled
(off):
Disabled
Heat max
4
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Cool min
4
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.2°C
Range:
54.0°F/12.2°C
to
100.0°F/37.7°C
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling.
Default:
2.0 min
Range:
0.0
to
5.0 min
adjustable in 1-minute increments
Set the anti-short cycle timer to
0.0 min
for equipment that already
has its own anti-short cycle timer.
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default:
4.0
Range:
3.0
or
4.0
cycles per hour
Table 2: Installer Configuration Menu (Part 2 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options