T600HCx-3 Single-Stage Thermostats Installation Instructions

12

To set the time schedule for a two-event schedule, 
follow the steps in Table 5. See Table 7, Events 1 
and 2, for an example of a two-event office schedule. 

Programming the Daily Schedule – Four-Event 
(T600HCP-3)

The schedule-setting menu is used to enter the 
occupied and unoccupied states for each day of the 
week. The schedule-setting menu reflects either a 
two- or four-event schedule per day, based on what 
was selected in the 

2/4event 

parameter during the 

configuration process. If the schedule-setting menu 
does not reflect a four-event schedule, select four 
events in the 

2/4event

 parameter of the Installer 

Configuration Menu.

When changing the time, press the 

UP/DOWN

 arrow 

keys once to change the time in 1-minute increments; 
press and hold down the keys to change the time in 
30-minute increments.

Note:

Programming one of the digital inputs to remote 

NSB disables the menu.

To set the time schedule for a four-event schedule, 
follow the steps in Table 6. See Table 7 for an example 
of a four-event office schedule.      

Table 5:  Programming the Daily Schedule – 

Two-Event (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key to all prompts until 

the schedule set prompt appears on 
the display. Press the 

YES

 key to 

enter the scheduling menu.

Press the 

YES

 key to set the 

schedule for Monday or press the 

NO

 

key to advance to Tuesday.

Press the 

YES

 key to set the 

occupied start time for Monday or 
press the 

NO

 key to advance to 

Tuesday. Selecting 

NO

 leaves the 

thermostat in the unoccupied state 
for the entire day.

Press the 

UP/DOWN

 arrow keys to 

set the occupied start time. Press the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the unoccupied start time. Press 
the 

YES

 key to enter the time.

Press the 

YES

 key to set the 

schedule for Tuesday or press the 

NO

 key to advance to Wednesday.

Press the 

YES

 key to copy the 

schedule from the previous day. 
Press the 

NO

 key to set a different 

schedule.

RoomTemp 
75.0

F

 

Schedule 
set? Y/N 

Monday 
set? Y/N 

Occupied 
day? Y/N 

Occupied 
12:00 AM 

Unoccup 
12:00 AM 

Tuesday 
set? Y/N 

Copy Y/N 
previous 

If the 

YES

 key was pressed, the next 

prompt is for Wednesday. Repeat the 
procedure for the rest of the days of 
the week.

After setting the schedule for all the 
days of the week, following the last 
entry for Sunday, press the 

YES

 key 

to return to the Status Display Menu 
or press the 

NO

 key to start again at 

Monday.

Table 6:  Programming the Daily Schedule – 

Four-Event (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key from the Status 

Display Menu to enter the Main User 
Menu.

Press the 

NO

 key to all prompts until 

the schedule set prompt appears on 
the display. Press the 

YES

 key to 

enter the scheduling menu.

Table 5:  Programming the Daily Schedule – 

Two-Event (Part 2 of 2)

Thermostat 
Display

Description

Wednesda
set? Y/N 

Exit?
 Y/N

 

RoomTemp
75.0

F

 

Schedule
set? Y/N 

Содержание T600HCN-3

Страница 1: ...nn es entrantes un quipement dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l quipement c...

Страница 2: ...at mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with t...

Страница 3: ...ion avant de r aliser tout raccordement lectrique afin d viter tout risque de d charge lectrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections...

Страница 4: ...conds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan is on The HEAT LED is on when heating is on The COO...

Страница 5: ...he scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each input can be configured to the Selection Options included in Table 2 Table 2 Installer Confi...

Страница 6: ...0 sec Frost pr Provides a minimum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat Default off on Enabled off Disabled Heat max4 Sets the Occupied and Unoc...

Страница 7: ...Main User Menu or DI1 or DI2 configured as a temporary override remote contact RemOVR Sets the effective duration of the Temporary heating or cooling setpoints set using the up down arrow keys defaul...

Страница 8: ...ve recovery is disabled if either DI1 or DI2 is configured as remote NSB Default off on Enabled provides the desired occupied temperature at the start of the occupied schedule off Disabled provides th...

Страница 9: ...DI2 is configured to operate as a remote override contact this menu is disabled To override the unoccupied state while in the Main User Menu 1 Press the NO key to all prompts until the Override Sched...

Страница 10: ...temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature...

Страница 11: ...ress the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to...

Страница 12: ...menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Press the YES key to set the occupied start time for Monday or press the NO key to advance to Tuesday S...

Страница 13: ...he UP DOWN arrow keys to set the second unoccupied start time Press the YES key to enter the time Press the YES key to set the schedule for Tuesday or press the NO key to advance to Wednesday Press th...

Страница 14: ...no alarm or backlight should be present If the day or time is incorrect repeat the Setting the Day and Time procedure Setting Schedule Hold The schedule hold menu is used to set a permanent hold on t...

Страница 15: ...hermostat fails to operate within its specifications replace the unit For a replacement thermostat contact the nearest Johnson Controls representative Table 8 Accessories Order Separately Code Number...

Страница 16: ...5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C bet...

Отзывы: