T600HCx-3 Single-Stage Thermostats Installation Instructions
8
2/4event
2
Sets the number of events within a
24-hour period.
Default:
2.0
(2.0):
Two events (one occupied and one unoccupied) within a
24-hour period
(4.0):
Four events (two occupied and two unoccupied) within a
24-hour period
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default:
n.o.
(n.c.):
Contact open = Occupied; contact closed = Unoccupied
(n.o.):
Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
Prog rec
2
Provides the desired occupied
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Note:
Progressive recovery is
disabled if either DI1 or DI2 is
configured as remote NSB.
Default:
off
(on):
Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off):
Disabled (provides the desired occupied temperature after the
occupied schedule begins)
1.
Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
schedules and the Schedule menu. (T600HCP-3 only)
2.
T600HCP-3 only.
3.
When adjusting the numeric value, press the
UP
or
DOWN
arrow key to change the value by single increments; press and
hold the
UP
or
DOWN
arrow key to change the numeric value in increments of ten.
4.
When adjusting the temperature, press the
UP
or
DOWN
arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the
UP
or
DOWN
arrow key to change the value in 5.0F°/5.0C° increments.
Table 2: Installer Configuration Menu (Part 4 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options