T600HCx-3 Single-Stage Thermostats Installation Instructions

3

Wiring

When an existing thermostat is replaced, remove and 
label the wires to identify the terminal functions. When 
a T600HCx-3 thermostat is replaced, simply remove 
the old screw terminal blocks and reinsert them onto 
the PCB of the replacement thermostat.        

To wire the thermostat:

1.

Strip the ends of each wire a 1/4 in. (6 mm) and 
connect them to the appropriate screw terminals as 
indicated in Figure 5.

2.

Carefully push any excess wire back into the wall. 
Seal the hole in the wall with fireproof material to 
prevent drafts from affecting the ambient 
temperature readings.

3.

Reinsert the screw terminal blocks onto the PCB.

4.

Reattach the thermostat cover to the mounting 
base (top side first).

5.

Use a Phillips-head screwdriver to reinstall the 
security screw on the bottom of the thermostat 
cover.    

!

CAUTION: Risk of Electric Shock.

Disconnect the power supply before 
making electrical connections to avoid 
electric shock.

MISE EN GARDE : Risque de décharge 
électrique.

Débrancher l'alimentation avant de 
réaliser tout raccordement électrique afin 
d'éviter tout risque de décharge 
électrique. 

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement. 

IMPORTANT:

Make all wiring connections in 

accordance with local, national, and regional 
regulations. Do not exceed the electrical ratings of 
the T600HCx-3 thermostat.

Figure 5: Terminal Blocks

4 pole left top connector

2 pole right top connector

Y1

G

RC

C

RH

W1

D1

D2

RS

Scom

6 pole bottom connector

OS MS

AUX

2

3

4

5

6

7

10

11

12

14

15

16

13

F

IG

:T

6

0

0

H

C

x

_

tr

m

b

lk

Figure 6: Wiring the T600HCx-3 Thermostats

Cool 1

Fan

24 VAC

Thermostat Power

Heat 1

Y1

G

RC

C

RH

W1

AUX

D1

D2

Scom

RS

Aux

If using the same power source
for the thermostat and heating
loads, install a jumper
across RC and RH.

Remote

Room

Sensor

Remote

Outdoor

Sensor

OS

F

IG

:T

6

0

0

H

C

P

_

w

ir

Isolated Contact
- Lighting
- On/Off Actuation
- Exhaust Fan

Содержание T600HCN-3

Страница 1: ...nn es entrantes un quipement dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l quipement c...

Страница 2: ...at mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with t...

Страница 3: ...ion avant de r aliser tout raccordement lectrique afin d viter tout risque de d charge lectrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections...

Страница 4: ...conds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan is on The HEAT LED is on when heating is on The COO...

Страница 5: ...he scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each input can be configured to the Selection Options included in Table 2 Table 2 Installer Confi...

Страница 6: ...0 sec Frost pr Provides a minimum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat Default off on Enabled off Disabled Heat max4 Sets the Occupied and Unoc...

Страница 7: ...Main User Menu or DI1 or DI2 configured as a temporary override remote contact RemOVR Sets the effective duration of the Temporary heating or cooling setpoints set using the up down arrow keys defaul...

Страница 8: ...ve recovery is disabled if either DI1 or DI2 is configured as remote NSB Default off on Enabled provides the desired occupied temperature at the start of the occupied schedule off Disabled provides th...

Страница 9: ...DI2 is configured to operate as a remote override contact this menu is disabled To override the unoccupied state while in the Main User Menu 1 Press the NO key to all prompts until the Override Sched...

Страница 10: ...temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature...

Страница 11: ...ress the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to...

Страница 12: ...menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Press the YES key to set the occupied start time for Monday or press the NO key to advance to Tuesday S...

Страница 13: ...he UP DOWN arrow keys to set the second unoccupied start time Press the YES key to enter the time Press the YES key to set the schedule for Tuesday or press the NO key to advance to Wednesday Press th...

Страница 14: ...no alarm or backlight should be present If the day or time is incorrect repeat the Setting the Day and Time procedure Setting Schedule Hold The schedule hold menu is used to set a permanent hold on t...

Страница 15: ...hermostat fails to operate within its specifications replace the unit For a replacement thermostat contact the nearest Johnson Controls representative Table 8 Accessories Order Separately Code Number...

Страница 16: ...5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C bet...

Отзывы: